Manual 26174
EGCP-2 Engine Generator Control Package
Woodward
101
Main Volt High Alarm
The Main Volt High condition will cause a response defined by this set point. The
available responses are:
Disabled
Warning
Loss of Mains
Loss of Mains with Alarms
Main Volt Low Limit
Alarms when Mains Voltage drops below set point.
Alarm can be set for Loss of Mains.
If Mains Voltage is below Low Limit, Mains are not considered stable, and
the EGCP-2 control will not issue a mains breaker closure command.
Main Volt Low Alarm
The Main Volt Low condition will cause a response defined by this set point. The
available responses are:
Disabled
Warning
Loss of Mains
Loss of Mains with Alarms
Main Frequency High Limit
Alarms when Mains Frequency exceeds Alarm Set Point.
Alarm can be set for Loss of Mains.
If Mains Frequency is above High Limit, Mains are not considered stable,
and the EGCP-2 control will not issue a mains breaker closure command.
Main Freq High Alarm
The Main Frequency High condition will cause a response defined by this set
point. The available responses are:
Disabled
Warning
Loss of Mains
Loss of Mains with Alarms
Main Frequency Low Limit
Alarms when Mains Frequency drops below set point.
Alarm can be set for Loss of Mains.
If Mains Frequency is below Low Limit, Mains are not considered stable,
and the EGCP-2 control will not issue a mains breaker closure command.
Main Freq Low Alarm
The Main Frequency Low condition will cause a response defined by this set
point. The available responses are:
Disabled
Warning
Loss of Mains
Loss of Mains with Alarms