Manual 26174
EGCP-2 Engine Generator Control Package
Woodward
205
Newage MA325
EGCP-2
NEWAGE
MA325
Voltage
Regulator
37
38
A2
A1
Voltage Regulator settings:
Droop - set for 2 to 5 %
In a multiple generator system, set
droop the same on all regulators
TRIM
Set TRIM pot fully Clockwise. This
will provide a 5% per volt change
on the accessory input.
Adjustment Procedure
1. Start the generator with the EGCP-2
NOT connected. Set the MA325 for rated
voltage
2. Connect the EGCP-2 as shown
3. Start Generator
4. Adjust the Volts Bias Offset for
rated voltage.
5. Press ENTER to save this value
6. Close the Voltage Raise discrete
input (4) and verify the EGCP2 can
move the generator voltage in the
increase direction.
7. Close the Voltage Lower discrete
input (5) to verify the EGCP-2 can drive
the generator voltage in the decrease
direction.
EGCP-2 settings:
Configuration Menu
Voltage Bias Type:
+/- 3 VDC
Calibration Menu
Volts Bias Offset:
0%
Shutdown & Alarms Menu
Gen Volt Hi Lmt:
* 10% above
rated
Gen Volt Lo Lmt:
* 10% below
rated
Reactive Load Control Menu
VAR/ PF Gain:
1.0
Volts Ramp Time:
100
VAR/ PF Sharing Gain:
0.2
VAR/ PF Stability:
2.0
PF Deadband:
0.005
* - These are only
suggested values