Manual 26174
EGCP-2 Engine Generator Control Package
Woodward
187
Basler KR2F, 4F, or 7F
EGCP-2
Basler
KR2F/FF
KR4F/FF
KR7F/FF
Voltage
Regulator
37
38
6
7
Voltage Trim
Potentiometer
500 ohm
Voltage Regulator settings:
Droop - set for 2 to 5 %
In a multiple generator system, set
droop the same on all regulators
Clockwise
Counter Clockwise
Adjustment Procedure
Start Generator
1. Set the Voltage Adjust potentiometer
on the KR regulator for Rated Voltage of
generator set. (course adjustment)
2. Use the Voltage Trim potentiometer
to fine tune the Rated Voltage. This is
the potentiometer shown above.
3. The Voltage Trim potentiometer is
now calibrated and should not be
adjusted anymore.
4. Close the Voltage Raise discrete
input (4) and verify the EGCP-2 can
move the generator voltage in the
increase direction.
5. Close the Voltage Lower discrete
input (5) and verify the EGCP-2 can
move the generator voltage in the
decrease direction.
6. The Reactive Load Menu items may
need adjusted for stable Power Factor
control.
EGCP-2 settings:
Configuration Menu
Voltage Bias Type:
+/- 3 VDC
Calibration Menu
Volts Bias Offset:
-45%
Shutdown & Alarms Menu
Gen Volt Hi Lmt:
* 10 above
rated
Gen Volt Lo Lmt:
* 10 below
rated
Reactive Load Control Menu
VAR/ PF Gain: 1.0
Volts Ramp Time:
200
VAR/ PF Sharing Gain:
0.2
VAR/ PF Stability:
2.0
PF Deadband:
0.005
* - These are only
suggested values
Voltage Trim Potentiometer:
500 ohm, 10 Turn, 1 Watt
Set to Mid-Range