Figure 4-8. kW Load Status
Generator KW
: The total, three phase kW the generator is producing.
Load Reference
: The load reference, in kW for the generator.
System Load
: The calculated system load for all units operating in isochronous
load sharing mode. This reading is NOT active in the Baseload mode.
Control
: The current load control state in operation. These states are:
OFF
DROOP
ISOCHRONOUS
BASELOAD
PROCESS
Process In
: The sensed value of the 4–20 mA or 1–5 Vdc process input. This
value will be displayed in an Engineering Unit that is configured in the Process
menu under Process Units.
Process Ref
: The process reference for the process control.
Master Sync Cmd
: The master synchronizing and load control bias command
(%).
Master Volt Cmd
: The master voltage bias command (%).
The master sync and master volt commands are only active in Slave
units that are in AUTO.