Manual 26174
EGCP-2 Engine Generator Control Package
Woodward
77
Voltage Reference
Range: 1—30000
Operating Voltage of Generator per Generator Nameplate.
Used for VAR/PF Sharing as the Reference that multiple generators share
reactive load to. This maintains the voltage reference while in Power Factor
Sharing or kVAR Control mode on an isolated bus.
Display Units
Range: American or Metric
Metric
Sets temperature readings to degrees Celsius (C), and pressure to bar
(BAR).
American
Sets temperature readings to degrees Fahrenheit (F), and pressure to
Pounds per Square Inch (psi).
Set Date
MM-DD-YY
Sets the date used by the control for Alarm / Event time stamps, and
displays.
Set Time
HH:MM
Sets the time used by the control for Alarm / Event time stamps, and
displays.
Start Sequencing
Range: Enabled or Disabled
Enabled
Uses Preglow time and Engine Crank.
Must have MPU to function.
Disabled
No Preglow Time or Engine Crank
Will operate without an MPU
Relay #12 Function
Range: kVA Load or Idle/ Rated Switch
kVA Load Switch
Defines Discrete Output #12 as a kVA load switch.
Uses kVA High and kVA Low value items in the Load Control Configuration
Menu.
Idle / Rated Switch
Defines Discrete Output #12 as an Idle / Rated speed switch. This output is
typically used to automatically send the engine speed control an idle/rated
command upon start up.
Uses the Idle Speed and Idle Time items in the Engine Control
Configuration Menu.