EGCP-2 Engine Generator Control Package
Manual 26174
62
Woodward
Figure 4-7. Synchronizer Status
Slip
: The slip frequency in Hz. of the generator in relation to the bus or mains it is
paralleling to.
Phase
: The phase angle difference in degrees between the generator and the
bus or mains it is paralleling to.
Volts
: The voltage differential in percent between the generator and the bus or
mains it is paralleling to.
Mains/Bus
: The active PT input being monitored by the EGCP-2.
Dead Bus
: Indicates if the PT input (mains or bus) being measured is dead.
Synchronizer Status
: Displays the state of the synchronizer. These states are:
CLOSE GEN BREAKER
SYNC TIMER
OPEN GEN BREAKER
IN SYNC
CLOSE MAIN BREAKER
SYNCHRO OFF
OPEN MAIN BREAKER
VB
: Voltage Bias Output (%)
SB
: Speed Bias Output (%)
GEN A
: Voltage of the generator.
MAINS
: Voltage of the active PT input being sensed by the synchronizer.
Generator and Mains voltage label, VLL—Voltage Line-to-Line or
VLN—Voltage Line-to-Neutral will be determined from the Voltage
Input configuration setting.
Generator and Mains voltage readings and labels will automatically
switch from “V” (volts) to “KV” (kilovolts), when the voltage exceeds
9999V for that input.
The synchronizer displays **** in the place of Slip, Phase, and Volts
when the synchronizer is inactive, or off.