EGCP-2 Engine Generator Control Package
Manual 26174
78
Woodward
Speed Bias Type
Range: ±3 Vdc, 0.5–4.5 Vdc, or 500 Hz PWM
±3 Vdc (WGC)
Sets the speed bias output to ±3 Vdc range. 0 Vdc is zero output,
–3 Vdc is –100% speed bias output,
+3 Vdc is +100% speed bias output.
0.5 to 4.5 Vdc (DDEC)
Sets the speed bias output to 0.5 to 4.5 Vdc range.
2.5 Vdc is zero,
0.5 Vdc is –100% speed bias output,
4.5 Vdc is +80% speed bias output.
500 Hz PWM (ADEM)
Sets the speed bias output to 500 Hz Pulse Width Modulated (PWM) range.
50% duty cycle = 0% speed bias output,
0% duty cycle = –100% speed bias output,
100% duty cycle = +100% speed bias output.
Voltage Bias Type
Range: ±1, 3, or 9 Vdc
±9 Vdc Bias
0 Vdc = 0% voltage bias
–9 Vdc = –100% voltage bias
+9 Vdc = +100% voltage bias
±3 Vdc Bias
0 Vdc = 0% voltage bias
–3 Vdc = –100% voltage bias
+3 Vdc = +100% voltage bias
±1 Vdc Bias
0 Vdc = 0% voltage bias
–1 Vdc = –100% voltage bias
+1 Vdc = +100% voltage bias
Circuit Breaker Control
Range: Breaker or Contactor
Defines action of Generator and Mains closure command.
Breaker issues momentary breaker close signal, and a separate momentary
breaker trip (open) signal. Get complete logic for Generator and Mains
breaker commands in chapter 3 under “Relay Outputs”.
Contactor issues continuous breaker close signal through the breaker close
relay output, DO2 for Generator and DO1 for the Mains.
Operating Mode
Range: Mains Parallel or No Parallel
Mains Parallel
will allow the unit to synchronize to the mains, and carry load
while in parallel with the mains as well (closed transition).
No Parallel
will not allow the unit to operate with load until the mains
breaker is sensed as being open (open transition).
All units operating in a load sharing system must be set for the same
parameter (that is, mains parallel, or no parallel).