
Manual 26174
EGCP-2 Engine Generator Control Package
Woodward
57
The screen displays the following information:
Alarms
: Number of active alarms on the unit.
Unit #
: The network address of the unit.
Mains
: A graphic display of the mains condition. Two minus symbols (--)
indicate the mains are out of spec, one plus symbol indicates the mains are in
spec, but not declared stable (+-), two plus symbols (++) indicate the mains are
in spec and stable.
Gen
: A graphic display of the status of the generator. Two minus symbols (--)
indicate the generator is out of spec, one plus symbol indicates the gen is in
spec, but not declared stable (+-) two plus symbols (++) indicate the generator is
in spec and stable.
Engine
: The operating state of the engine.
Engine Control States:
OFF
PREGLOW
CRANK
RUN
COOLDOWN
SPINDOWN
RETRY
Operating State
: Shows if the EGCP-2 is in AUTO or MAN (manual) mode.
Load Control State
: Shows the state of the load control logic of the EGCP-2.
The load control states are:
Load
Control
States:
OFF
DROOP
ISOCHRONOUS
BASELOAD
PROCESS
KW
: The total kW load on the generator.
Hz
: The frequency, in Hertz, of the generator set.
PF
: The average three phase power factor of the generator set.
KW-Hrs
: The total accumulated kW hours produced by the generator set. This
display automatically switches to MW-Hrs when the kW-Hour value exceeds 10
000. Display is updated every 0.1 MW-Hrs.
Run-Time
: The total accumulated run time of the generator set. Display is
updated every run hour.
All the display information will update automatically as operating modes and
conditions to the EGCP-2 change.