EGCP-2 Engine Generator Control Package
Manual 26174
164
Woodward
Sequencing
Problem Probable
Cause
Corrective
Action
Unit number(s) does not
show up in the sequencing
order in the sequencing
screen/unit doesn’t auto
sequence
switch in manual position
Switch unit(s) to the Auto
switch active position. See
dc inputs/outputs.
Automatic sequencing set
point in the configuration
menu set to disabled
ENABLE the Automatic
sequencing set point in the
configuration menu. See
description of set points.
Unit has an active alarm
Commit or reset alarm
condition(s). See
description of screens.
RS-485 Network not
connected at unit(s)
Verify that the RS-485
network is connected to all
EGCP-2 controls in system.
RS-485 Network is
inadequately terminated
Verify that the RS-485
Network is correctly
terminated. See inter-
control communications
(RS-485).
When system load is large
enough to require additional
gen-sets, more than one set
is sequenced on line
NEXT GENSET DELAY set
point in sequencing menu is
too short
Increase NEXT GENSET
DELAY set point in
sequencing menu. See
description of set points.
MAX START TIME set point
in sequencing menu is too
short
Increase MAX START TIME
set point in sequencing
menu. See description of
set points.
When system load is small
enough to take additional
sets off line, more than one
set is sequenced off line
REDUCED LOAD DELAY
set point in sequencing
menu is too short
Increase REDUCED LOAD
DELAY set point in
sequencing menu. See
description of set points.
MAX STOP TIME set point
in sequencing menu is too
short
Increase MAX STOP TIME
set point in sequencing
menu. See description of
set points.