EGCP-2 Engine Generator Control Package
Manual 26174
48
Woodward
AC Inputs
The EGCP-2 receives ac inputs from the generator, bus, mains and engine. They
are as follows:
Location Description
Signal
Burden
42
Generator PT phase A +
AC Voltage
200 k
Ω
43
Generator PT phase A –
AC Voltage
A+ to A–
44
Generator PT phase B +
AC Voltage
200 k
Ω
45
Generator PT phase B –
AC Voltage
B+ to B–
46
Generator PT phase C +
AC Voltage
200 k
Ω
47
Generator PT phase C –
AC Voltage
C+ to C–
89
Generator CT phase A+ Current
AC Current
0.050
Ω
90
Generator CT phase A– Current
AC Current
+ to –
91
Generator CT phase B+ Current
AC Current
0.050
Ω
92
Generator CT phase B– Current
AC Current
+ to –
93
Generator CT Phase C+ Current
AC Current
0.050
Ω
94
Generator CT Phase C– Current
AC Current
+ to –
40
Mains/Bus PT Phase A
AC Voltage
200 k
Ω
41
Mains/Bus PT Phase B or N
AC Voltage
+ to –
70
Magnetic
AC Frequency
15 k
Ω
71
Magnetic Pickup –
AC Frequency
+ to –
72
Magnetic Pickup Shield
DC Inputs and Outputs
Location Description
Signal
I/O
1
+ power supply
9–32 Vdc
Isolated
2
– power supply
Input 13 W typical,
20 W max.
86
+ Process Signal
4–20 mA
Isolated Input
87
– Process Signal
or 1–5 Vdc
249
Ω
(4–20 mA)
88
Process Signal Shield
30 k
Ω
(1–5 Vdc)
73
+ Speed Bias
±3 Vdc,
Software Configured
74
– Speed Bias
0.5 to 4.5 Vdc,
10 mA Maximum
75
Speed Bias Shield
500 Hz PWM
Isolated Output
37
+ Voltage Bias
±1, 3, or 9 Vdc
Software Configured
38
– Voltage Bias
10mA Maximum
39
Voltage Bias Shield
Isolated Output
68
Pressure
0–200
Ω
sensor,
Internal Voltage Source
69
Pressure Sensor –
4-20 mA, or 1-5 Vdc Internal Source Common
Dip Switch Selected
66
Temp
0–200
Ω
sensor
Internal Voltage Source
67
Temp Sensor –
4–20 mA, or 1–5 Vdc Internal Source Common
Dip Switch Selected