English
36
WILO SE 07/2019
Pump is not stable and/or making
unusual noises
Connection pipe between VBH and pump
blocked or shut off
Check the connection pipe, if necessary,
remove the clogging or open the shut-off
device
Air in the inlet
Check and shut off the piping and vent the
pumps if necessary
Air in the pump
Vent the pump, check the suction line for
leakages and seal it if necessary
Air in the pump due to insufficient level in
the tank
Check the level in the tank. If necessary,
readjust the float valve
Air in the pump due to blocked bypass
line
Check the bypass line, if necessary, remove
the clogging or open the shut-off device
Impellers are blocked
Check the pump and replace it or have it
repaired if necessary
Flow rate is too high
Check the pump data and default values and
correct them if necessary
Incorrect direction of rotation of the
motors
Check direction of rotation and correct by
changing over phases if necessary
Pump is not stable and/or making
unusual noises
Mains voltage: a phase is missing
Check the fuses, cables and connections
Pump is not adequately secured to base
frame
Check the fixation and re-tighten the
fastening screws if necessary
Bearing damage
Check the pump/motor and replace it or have
it repaired if necessary
Motor or pump become too warm
Air in the inlet
Check, seal the pipeline if necessary, bleed
the pumps, check the level in the tank
Bypass line is closed or not sufficiently
open
Check, also check the bypass passage if
necessary
Impellers are blocked
Check the pump and replace it or have it
repaired if necessary
Bearing damage
Check the pump/motor and replace it or have
it repaired if necessary
Turn-to-turn fault in the motor
Check and, if necessary, replace the motor or
have it repaired
Mains voltage: a phase is missing
Check the fuses, cables and connections
Current consumption is too high
Flow rate is too high
Check the pump data and default values and
correct them if necessary
Turn-to-turn fault in the motor
Check and, if necessary, replace the motor or
have it repaired
Mains voltage: a phase is missing
Check the fuses, cables and connections
Motor protection switch triggers
(fault only occurs in test
operation)
Non-return valve is defective
Check and replace the non-return valve if
necessary
Flow rate is too high
Check the pump data and default values and
correct them if necessary
Power contactor is defective
Check it and replace it if necessary
Turn-to-turn fault in the motor
Check and, if necessary, replace the motor or
have it repaired
Mains voltage: a phase is missing
Check the fuses, cables and connections
Pump generates no or insufficient
power
Inlet pipe is blocked or shut off
Check the inlet pipe and remove the block-
age or open the shut-off device if necessary
Air in the inlet
Check and shut off the piping and vent the
pumps if necessary
Impellers are blocked
Check the pump and replace it or have it
repaired if necessary
Non-return valve is leaking
Check and replace the seal or non-return
valve if necessary
Non-return valve is blocked
Check and remove the blockage or replace
the non-return valve if necessary
Gate valve in the system is closed or not
sufficiently open
Check and open the shut-off device
completely if necessary
Pump generates no or insufficient
power
Incorrect direction of rotation of the
motors
Check direction of rotation and correct by
changing over phases if necessary
Turn-to-turn fault in the motor
Check and, if necessary, replace the motor or
have it repaired
Fault
Cause
Remedy
Summary of Contents for FLA Compact-1 Helix V16
Page 2: ...Fig 1a Fig 1b...
Page 3: ...Fig 2a Fig 2b...
Page 4: ...Fig 3...
Page 5: ...Fig 4a...
Page 6: ...Fig 4b C Fig 5...
Page 7: ...Fig 6a Fig 6b...
Page 8: ...Fig 7a Fig 7b...
Page 9: ...Fig 8a...
Page 10: ...Fig 8b...
Page 11: ...Fig 9a Fig 9b...
Page 12: ...Fig 10a Fig 10b...
Page 13: ...Fig 10c Fig 10d...
Page 14: ...Fig 11...
Page 55: ...Fran ais Notice de montage et de mise en service Wilo FLA Compact 41...
Page 73: ...Fran ais Notice de montage et de mise en service Wilo FLA Compact 59...