5.3 Scope of delivery
• Fire-extinguishing system Wilo-FLA Compact
(system with switchgear, pump(s) and break tank)
• Installation and operating instructions for the fire-
extinguishing system Wilo-FLA Compact
• Installation and operating instructions for the
pumps
• Installation and operating instructions for the
control device
• Factory acceptance test certificate
(in accordance with EN10204 3.1.B)
• Installation plan (if applicable)
• Electrical circuit diagram (if applicable)
• Installation and operating instructions for the
signal transmitter (if applicable)
• Spare parts list (if applicable)
• Additional documentation for special versions
(if applicable)
5.4 Accessories
Accessories must be ordered separately as
required. The accessories from the Wilo range
include the following:
• Flexible connection pipes
• Compensators
• Threaded flange
• Diaphragm expansion tank
• Flushing apparatus kit in accordance with
DIN 1988-600
5.2
Technical data
Max. volume flow
See catalogue/data sheet
Max. delivery head
See catalogue/data sheet
Speed
2800 – 2900 rpm
Mains voltage
3~ 400 V ±10 % V (L1, L2, L3, PE)
Rated current
See rating plate
Frequency
50 Hz
Electrical connection
Insulation class
F
Protection class
IP54
Power consumption P
1
See rating plate of pump/motor
Power consumption P
2
See rating plate of pump/motor
Permitted ambient temperature
5 °C to 40 °C
Approved fluids
Pure water without settling sediments
Admissible fluid temperature
3 °C to 50 °C
Maximum permitted operating pressure
On the pressure side 10/16 bar (DS8 to PN 10; DS16 to PN 16)
Max. permissible inlet pressure
See inlet pressure fresh water
Nominal diameters
Connection replenishment valve on the
break tank FLA Compact-1
G2 (Helix V 16.. / Helix V 22..).
Connection replenishment valve on the
break tank FLA Compact-2
2 x G 2 (Helix V 1612 / Helix V 22..).
Pressure pipe connection FLA Compact-1
R 1½ (Helix V 1604 - 1611)
R 2 (Helix V 1612 / Helix V 22..)
Pressure pipe connection FLA Compact-2
R 2½ (Helix V 1604 - 1611)
R 3 (Helix V 1612 / Helix V 22..).
Break tank
Material
Polyethylene (PE-HWU) black
Ambient temperature
5 °C to +40 °C
Empty -20 °C to +60 °C
Float switch (protection against low water
level; overflow signal transmitter)
Max. switching voltage
48 V
Max. switching current
0.5 A
Max. switching capacity
3 W / 3 VA
Material
PVC
Protection class
IP67
Further data...
Diaphragm pressure vessel
8 l (see rating plate diaphragm expansion tank)
Summary of Contents for FLA Compact-1 Helix V16
Page 2: ...Fig 1a Fig 1b...
Page 3: ...Fig 2a Fig 2b...
Page 4: ...Fig 3...
Page 5: ...Fig 4a...
Page 6: ...Fig 4b C Fig 5...
Page 7: ...Fig 6a Fig 6b...
Page 8: ...Fig 7a Fig 7b...
Page 9: ...Fig 8a...
Page 10: ...Fig 8b...
Page 11: ...Fig 9a Fig 9b...
Page 12: ...Fig 10a Fig 10b...
Page 13: ...Fig 10c Fig 10d...
Page 14: ...Fig 11...
Page 55: ...Fran ais Notice de montage et de mise en service Wilo FLA Compact 41...
Page 73: ...Fran ais Notice de montage et de mise en service Wilo FLA Compact 59...