English
Installation and operating instructions Wilo-FLA Compact
33
• After setting the pressure switch, secure it against
unauthorised adjustment (e.g. sealing).
The
pressure switch of type FF4
is designed as a
single-pole changeover contact. The switch con-
tact is wired at the factory to open when the pres-
sure drops and close when the set pressure is
reached (the pump runs with the switch contact
open).
8.1.1 Default values for the pressure switch
H(Q0) … zero-delivery head of the system
H(geo)… geodesic head difference between
highest fire hose reels and FLA Compact
DS..A … switch-off pressure of the relevant
pressure switch(..)
DS..E … start-up pressure of the relevant
pressure switch(..)
Setpoint… specified operating pressure of
FLA Compact
NOTICE!
H(Q0) can be found in the enclosed test report
for the FLA Compact.
FLA Compact-1 (Fig. 2a):
Start-up pressure = setpoint
Switch-off pressure = H(Q0) – 0.5 bar
Example:
H(Q0) = 75 m (~7.5 bar)
Setpoint = 6 bar
H(geo) = 20 m (~2.0 bar)
FLA Compact-2 (Fig. 2b):
H(Q0) > DS1A
≥
DS2A > DS1E
≥
DS2E
≥
DS3A >
DS3E
NOTICE!
The default value for pressure switch 3 ON
depends on the system’s hydraulic ambient varia-
bles; however, it should be within the limit values
“min” and “max” in Table 5.
Example:
H(Q0) = 75 m (~7.5 bar)
Setpoint = 6 bar
H(geo) = 20 m (~2.0 bar)
Pressure switch 1 (item 12)
ON
DS1E
OFF
DS1A
Setpoint
H(Q0) – 0.5 bar
Table 4
Pressure switch 1
DS1E
DS1A
6.0 bar
7.0 bar
Pressure switch 1 (item 12a)
Pressure switch 2 (item 12b)
Pressure switch 3 (item 12c)
ON
DS1E
OFF
DS1A
ON
DS2E
OFF
DS2A
ON
DS3E
OFF
DS3A
Setpoint
H(Q0) – 0.5 bar
DS1E
DS1A
min.: H(geo) + 0.5 bar
max.: Setpoint – 0.5 bar
DS2E
Table 5
Pressure switch 1
Pressure switch 2
Pressure switch 3
DS1E
DS1A
DS2E
DS2A
DS3E
DS3A
6.0 bar
7.0 bar
6.0 bar
7.0 bar
2,5 … 5,5 bar
6.0 bar
Summary of Contents for FLA Compact-1 Helix V16
Page 2: ...Fig 1a Fig 1b...
Page 3: ...Fig 2a Fig 2b...
Page 4: ...Fig 3...
Page 5: ...Fig 4a...
Page 6: ...Fig 4b C Fig 5...
Page 7: ...Fig 6a Fig 6b...
Page 8: ...Fig 7a Fig 7b...
Page 9: ...Fig 8a...
Page 10: ...Fig 8b...
Page 11: ...Fig 9a Fig 9b...
Page 12: ...Fig 10a Fig 10b...
Page 13: ...Fig 10c Fig 10d...
Page 14: ...Fig 11...
Page 55: ...Fran ais Notice de montage et de mise en service Wilo FLA Compact 41...
Page 73: ...Fran ais Notice de montage et de mise en service Wilo FLA Compact 59...