5/12/2017
TECH-538/D.W.O. 23160
Page 175 of 189
Message
Meaning
Solution
Error: Const.
position or
stuck valve
Problems in the
movement
detection
during
calibration
Check:
The position sensor (Hall-effect sensor) connector and cable. .
See Figure 5-1 and find the connector J6 for local or remote
sensor connection for the ICoT 5400. See
Figure 6-3 and find the connectors J3 and J4 for remote
sensor connection for the ICoT 6400. The connector J2 is
used for local sensor connection for the ICoT 6400.
•
Magnet assembly:
o
For rotary magnets check if it is not rotated 90
degrees
o
For linear magnets, check if the magnet assembly
center is matching the actuator mid position.
•
Pressure supply stability.
•
Actuator and tubing leaks.
•
Manifold and transducer assembly are tightly coupled to
the enclosure and there are no leaks.
•
Check if the cable between the inner canister and the
pneumatic transducer assembly is tightly connected.
•
Actuator/Valve assembly integrity.
•
Try to repeat a full auto CAL.
•
Call Westlock- for additional support.
Sensor err:
not possible
set gain
down
The calibration
of the position
sensor could
not find a
proper gain to
work with the
current Position
Sensor and
magnet
assembly
Check:
The position sensor (Hall-effect sensor) connector and cable. .
See Figure 5-1 and find the connector J6 for local or remote
sensor connection for the ICoT 5400. See
Figure 6-3 and find the connectors J3 and J4 for remote
sensor connection for the ICoT 6400. The connector J2 is
used for local sensor connection for the ICoT 6400.
•
Magnet assembly is in correct position:
o
For rotary magnets check if it is not rotated 90
degrees
o
For linear magnets, check if the magnet assembly
center is matching the actuator mid position.
Check if the proper fail-down or fail-up magnet is
being used
•
Try to repeat a full auto CAL
•
Try to replace the Position Sensor and/or the magnet
•
Remove power for at least 1 minute and retry
•
Remove power for at least 1 minute, perform a factory
default initialization (see Section 9.2.2.4) and retry a full
auto CAL
•
Call Westlock- for additional support.
Sensor err:
not possible
set gain up