5/12/2017
TECH-538/D.W.O. 23160
Page 149 of 189
Index
Std.
Par.
Parameter mnemonic
Description / EDD Help
Valid Range
FF Default
FCT Default
Deep
Default
Units
Write
R/W
final position value is passed back to
connected function block.
Enumerations defined in Standard
Tables (TN-016).
1: Working Position
Value
Value
Position
Value
Position
Value
36
PSNR_COMMAND
Command to start device-specific
procedure. Command value will reset
to zero after execution of procedure
regardless of value of
PSNR_COMMAND_STATE.
0: Normal Operation
1-7: Reserved
8-65535:Mfg Specific,
as following:
2048, 0X0800
: "Arm"
2304, 0X0900
: "Start
Auto Cal"
2560, 0X0A00
: "Start
Position Sensor Cal"
2816, 0X0B00
: "Start
Low/Zero Cal"
3072, 0X0C00
: "Start
High/Span Cal"
3328, 0X0D00
: "Start
Transducer Cal"
3584, 0X0E00
: "Start
Auto PID Tuning"
3840, 0X0F00
: "Abort"
0: Normal
Operation
0: Normal
Operation
0: Normal
Operation
E
O/S,
Man
R/W
37
PSNR_COMMAND_STATE
The state of the procedure initiated
by PSNR_COMMAND.
0: Normal Operation
1-7: Reserved
8-65535:Mfg Specific,
as following:
2048, 0X0800
: "Arm"
2304, 0X0900
: "Start
Auto Cal"
2560, 0X0A00
: "Start
Position Sensor Cal"
2816, 0X0B00
: "Start
Low/Zero Cal"
3072, 0X0C00
: "Start
High/Span Cal"
3328, 0X0D00
: "Start
Transducer Cal"
3584, 0X0E00
: "Start
Auto PID Tuning"
3840, 0X0F00
: "Abort"
0: Normal
Operation
0: Normal
Operation
0: Normal
Operation
E
Read
only
38
PSNR_OOS_OPT
Defines an action to be taken
whenever the Transducer Block
0: Hold Last Value
1: Fail Closed
1: Fail Closed
1: Fail
Closed
1: Fail
Closed
E
O/S,
Man
R/W
32
See also 9.2.3.12 for power failure condition