5/12/2017
TECH-538/D.W.O. 23160
Page 150 of 189
Index
Std.
Par.
Parameter mnemonic
Description / EDD Help
Valid Range
FF Default
FCT Default
Deep
Default
Units
Write
R/W
transitions to Out of Service mode.
*Note: not all options are required to
be supported.
2: Fail Open
3:
PSNR_FSTATE_VAL_D
4-7: Reserved
8-255: Mfg Specific
39
POS_FEATURES
BIT_ENUMERATED parameter
indicating the parameter groups
supported by this transducer block.
0: Group A
1: Group B
2: Group C
3: Group D
4: Group E
5: Group F
6: Group G
7: Group H
8: Group I
9: Group J
10: Group K
11: Group L
12-15 Reserved
A, C, D, K, L
A, C, D, K, L
A, C, D, K, L E
Read
only
40
ACT_FAIL_ACTION
Informative parameter, does not
affect the block. Specifies the final
failure position of the actuator as
defined in the Standard Tables (TN-
016). It is a recommendation that
only the first four enumerations of
the Last Va; table be used.
0: Undefined
1: Self-closing
2: Self-opening
3: Hold last value
4: Maximum value
5: Minimum value
255: Indeterminate
0
0
0
E
R/W
41
ACT_MAN_ID
The actuator manufacturer
identification.
None
R/W
42
ACT_MODEL_NUM
The actuator model number.
None
R/W
43
ACT_SN
The actuator serial number.
None
R/W
44
Y
ACT_TYPE
Actuator type, just and informative
parameter.
0: Undefined
1: Linear
2: Rotary
3: Rotary - Multi-turn
4: Rotary - Quarter-
turn
5: Linear - Lever
6-32767: Reserved
32768-65534:
Manufacturer Specific
2: Rotary
2: Rotary
2: Rotary
R/W
45
VALVE_MAN_ID
The valve manufacturer
identification.
None
R/W
46
VALVE_MODEL_NUM
The valve model number.
None
R/W
47
VALVE_SN
The valve serial number.
None
R/W
48
VALVE_TYPE
The type of the valve as defined in
the Standard Tables (TN-016).
0: Globe
1: Gate
2: Butterfly
3: Ball
4: Plug
2: Butterfly
2: Butterfly
2: Butterfly E
R/W