FB081TF R404A REFRGERANT CHART
Characteristics vary depending on operating conditions.
24 hour mroduction
R-404a ce Production
Air Temperature/
Water Temperature
24 Hour Ice
Production
kWh/100 lbs (45 kg)
@ 90°/70°F (32°/21°C)
70°/50°F
(21°/10°C)
261 lbs
(118 kg)
8.69
90°/70°F
(32°/21°C)
185 lbs
(84 kg)
Water usage/100 lbs./45.4 kgs of Ice
Potable Water: 12 gallons, 45.4 liters
Omerating temmeratures R404A
Air Temmerature
Around the Unit
Discharge
Temmerature
At Commressor
Suction
Temmerature At
Commressor
70°F
21° C
180-190
82-88
32-37
0-3
90° F
32° C
205-215
96-102
38-43
3-6
110° F
43° C
227-237
108-114
40-45
4-7
Due to the critical refrigerant amount, verify operational
temperatures with an electronic thermometer.
All discharge and suction line temperature readings are
taken within 6” of the compressor.
Install gauges only when necessary to diagnose failed
components.
Omerating Pressures R404A
Air Temmerature
Around the Unit
°F/°C
Discharge Pressure
PS
kPa
Suction Pressure
PS
kPa
70/21
210-230
1448-1586
28-33
193-228
90/32
290-310
1999-2137
32-37
221-255
110/43
355-375
2448-2586
36-41
248-283
FB081TP R290 REFRGERANT CHART
Characteristics vary depending on operating conditions.
24 hour mroduction
Air Temmerature
Water Temmerature
°F/°C
24 hour Production
70°/21°
50°/10°
591 lbs
268 kgs
90°/32°
70°/21°
451 lbs
204 kgs
Omerating temmeratures R290
Air Temmerature
Around the Unit
Discharge
Temmerature
At Commressor
Suction
Temmerature At
Commressor
70°F
21° C
180-190
82-88
30-35
-1 - 2
90° F
32° C
205-215
96-102
36-41
2-5
110° F
43° C
135-146
113-118
40-45
4-7
Due to the critical refrigerant amount, verify operational
temperatures with an electronic thermometer.
All discharge and suction line temperature readings are
taken within 6” of the compressor.
Install gauges only when necessary to diagnose failed
components.
Omerating Pressures R290
Air Temmerature
Around the Unit
°F/°C
Discharge Pressure
PS
kPa
Suction Pressure
PS
kPa
70/21
160-180
71-82
22-28
-6 - -2
90/32
205-225
96-107
23-29
-5 - -2
110/43
275-295
135-146
26-32
-3 - 0