Part Number REV00 04/08/2020 77
Refrigerated Cabinet
TEMPERATURE THERMISTOR - NOZZLE & CABINET PROBES ONLY
Location
• Nozzle Thermistor - Behind the front fascia inside the
duct area connected to the product line.
• Cabinet Thermistor - Attached to the evaporator plate in
the base unit.
• Defrost Thermistor - Inserted into the evaporator coil.
Function
Supplies input to the SRB board to indicate nozzle, cabinet
or defrost temperature. The SRB board energizes and
de-energizes the compressor based on input from the
thermistors.
Specifications
5,000 Ohms ± 2% at 25°C (77°F)
16,330 Ohms ± 2% at 0°C (32°F)
Check Procedure
NOTE: Use a multimeter to check operation.
1. Reboot machine by moving toggle switch off/on.
2. Inspect for correct wiring on the SRB Board.
• Nozzle connection terminal J33
• Cabinet connection terminal J32
• Defrost connection terminal J34
3. Isolate by disconnecting the wiring connectors.
4. Check continuity across the terminals with an ohm
meter.
• Resistance = Thermistor is good.
• Open (OL) = Replace thermistor.
NOTE: These thermistors are identical. Swapping the
thermistor connections at the SRB board can be used for
diagnostics.
Temperature/Resistance Chart
This chart is used for the temperature control thermistors.
As the temperature rises at the thermistor block, the
resistance drops.
If the ohmmeter reads “OL”, check the scale setting on the
meter before assuming the thermistor is bad.
°C
°F
OHM
-17.8
0
43,297
-15.0
5
36,503
-12.2
10
30,884
-9.4
15
26,948
-6.7
20
22,928
-3.9
25
20,082
-1.1
30
17,188
1.7
35
14,751
4.4
40
13,019
7.2
45
11,506
10.0
50
9,951