Part Number REV00 04/08/2020 41
Refrigerated Cabinet
REFRIGERATED CABINET FLOWCHART
Power Supplied?
Switch In ON Position?
Move Switch To ON Position
Plug In, Reset Breaker
No
Yes
No
Yes
Touch Screen
Energized?
No
Yes
Refer To Touch Screen Diagnostics
Yes
Refrigerator Is
Warm?
No
Evaporator Fans
Energized?
NO
Yes
Refrigerator Is
Freezing Product?
Replace Thermostat
Too Much Warm Product,
Too Many Door Openings,
Ice On Evaporator Coil
Duct Fan Not Energized
Defective Thermistor
Adjusting Opens
Thermostat?
Verify New Setting Cycles
Machine On/Off
No
Yes
No
Yes
Replace Motor
Power To Fan Motor?
Repair Wiring
Shaft Turns?
Replace Fan Blade
No
Yes
No
Yes
Yes
Temperature Set To 36º
No
Refer To Control
Board Diagnostics
Temperature Set
Too High?
Reset Temperature
Adjusting Temperature
Starts Compressor?
Check Thermistor Mounting &
Refer To Thermistor Diagnostics
Yes
No
No
Yes
Compressor Starts
After 15 Minutes
No
Yes
No
Yes
Verify:
Compressor Overload is Closed
Start Components Function
Condenser Fan Motor Functions
Voltage Must Be Within 10% Of Nameplate At
Compressor Startup
Compressor Starts
After 3 Minutes?
Compressor On?
No
Compressor Anti Short Cycle Delay Is 3 Minutes
Yes
Yes
Defrost Cycle Was Initiated:
Determine Cause Of 3 Hour
Continuous Compressor Run Time
Clean The Condenser Coil
Check Clearances
High Ambient
Yes