Part Number REV00 04/08/2020 37
DISCHARGE PRESSURE HIGH CHECKLIST
Air Condenser
• Dirty condenser filter
• Dirty condenser fins
• High inlet air temperature
• Condenser discharge air recirculation
• Defective fan cycling control
• Defective fan motor
Other
• Overcharged
• Non-condensable (air) in system
• Wrong type of refrigerant
• Non-OEM components in system
• High side refrigerant lines/component restricted
DISCHARGE PRESSURE LOW CHECKLIST
Air Cooled Condensers
• Defective fan cycle control, stuck closed
Other
• Undercharged
• Wrong type of refrigerant
• Non-OEM components in system
SUCTION PRESSURE HIGH CHECKLIST
Improper Installation
• Refer to “Installation/Visual Inspection Checklist”
Discharge Pressure
• Discharge pressure is too high and is affecting suction
pressure
Improper Refrigerant Charge
• Overcharged (also see “Freeze Cycle Discharge Pressure
High Checklist” )
• Wrong type of refrigerant
• Non condensible in system
Components
• TXV flooding
• Defective compressor
Other
• Non-OEM components in system
SUCTION PRESSURE LOW CHECKLIST
Improper Installation
• Refer to “Installation/Visual Inspection Checklist”
Discharge Pressure
• Discharge pressure is too low and is affecting low side –
refer to “Freeze Cycle Discharge Pressure Low Checklist”
Improper Refrigerant Charge
• Undercharged
• Wrong type of refrigerant
Other
• Non-OEM components in system
• Restricted/plugged liquid line drier
• Restricted/plugged tubing in suction side or liquid line
of refrigeration system
• TXV starving