Part Number REV00 04/08/2020 45
REACH-IN TEMPERATURE OUT OF RANGE
Check Refrigeration System & Door Seal
Temperature in reach-in unit above or below acceptable
limits.
Above temperature limit:
• Verify Cabinet temperate is above 5.5°C/42°F.
• Compare temps on UI (User Interface).
• Check duct fan (1) for proper operation.
• Check evaporator fans (3) for proper operation.
Duct Fan Motor
Evaporator Fan Motors
Evaporator Coil
• Verify door is closed and door gasket is in place.
• If all above are within Spec’s refer to Refrigeration
diagnostics. See “Refrigeration System Diagnostics” on
Below temperature limit:
• Compare temps on UI (User Interface).
• Check temperature set point.
• Using the touch screen, go to the Service or Managers
Menu on the Main Screen.
A
• Touch Service Inputs > Temperatures to view current
temperature readings.
A
• Touch Service Inputs > Refrigeration to view current
refrigeration cabinet settings.
• Touch Settings > Cabinet to make changes to the
default refrigerated cabinet values.