In addition, this parameter determines how an interrupted se-
quence can still be continued:
-
Only by object
The sequence can only be continued by object 53.
-
After off-time
The sequence is continued after the set off-time.
-
On next activated step
The sequence is continued with the next activated
step, the next step can be activated by object or time-
controlled.
Off-time
Only visible if the sequence is to be continued after off-time, with
this parameter the off-time can be configured.
Step after man. operation
This step is executed when resuming after manual operation, the
function of the set step is always executed, regardless of its oth-
erwise set starting conditions.
Polarity of objec
t “Sequence on/off“
This parameter can be used to set the telegram value with which
the sequence can be switched on and off via object 54. If the se-
quence is switched off, any further activation of a step is disa-
bled.
Behavior on switching on
Here it is determined how the sequencer behaves when
switched on by object 54:
-
No reaction
No function is executed, the sequencer waits for steps
to be activated.
-
Step x
The function of the step is executed (independent of
the other set start conditions of the step), the se-
quence is then continued according to its configuration
from this step onwards.
Switching on also reactivates a sequence interrupted by manual
operation.
Behavior on switching off
Here it is determined how the sequencer behaves when
switched off by object 54:
-
Complete actual step
If the sequencer is in a dimming process, it is com-
pleted.
-
Step x
The function of the step is executed (independent of
the other set start conditions of the step).
-
Stop immediately
If the sequencer is in a dimming process, it is stopped.
Apart from the set behavior when switching off, any further acti-
vation of a step after switching off is disabled until the sequencer
is switched on again by object 54.
Step 1-32
When a step is activated, its parameters for configuration ap-
pear.
In the text box at the top right with the content "Step x", you can
enter your own name for the step. This designation serves for
better orientation of the user and has no influence on the func-
tion of the step.
Start by time
This parameter is used to configure a temporal start condition of
the step.
-
Disabled
Start condition not used
-
Start at a fixed time of day
Here the time of day at which the step should start can
be entered. When using this start condition, the current
time must have been received via the following object:
Group Object
Type KNX
Size
Direction
GO 5 Time of Day - Set
10.001
3 Byte
From KNX
If no valid time was received by object 5, all
start conditions at fixed times of day are not
active.
The time is continuously updated by the de-
vice through its internal timers, but compo-
nent tolerances always result in a deviation
from the actual time. Therefore, the current
time should be sent to the device by a pre-
cise timer at least twice a day in order to
keep the deviation as small as possible.
-
Start after last trigger
Here you can specify the time interval to wait after the
previous activation before executing the step. This
start condition is not available for step 1.
Start time
Here either the time day or the waiting time can be specified for
the execution of the current step, if a timed start condition is
used.
Start by ON/OFF telegram
When using this start condition, a separate object is available for
each step:
Group Object
Type KNX
Size
Direction
GO 55-86 RGB A: Sequence Step x
on/off - Switch
1.001
1 Bit
From KNX
An ON telegram to one of these objects activates the respective
step, the sequence is then continued according to its configura-
tion from this step onwards.
An OFF telegram also activates this step, but resets the se-
quence at the same time.