2019 WEINZIERL ENGINEERING GmbH
Page 31/41
Group Object Dimmer D
Type KNX
Size
Direction
GO 356 Dimmer D: Dimming output -
State On/Off
1.001
1 Bit
To KNX
GO 357 Dimmer D: Dimming output -
State value
5.001
1 Byte
To KNX
Time for cyclic state
With this parameter, the cycle time can be set, when “Cyclic and
on change“ is selected for sending state.
Behavior on bus power failure
The behavior of the output in the event of bus power failure can
be configured here.
The following options are selectable:
-
No reaction
-
Dim to value
A parameter for adjusting the value appears.
Behavior after bus power return
Here the behavior of the output after bus power return can be
configured. This behavior will be set after every device restart
(e.g. also on restart after ETS download).
The following options are selectable:
-
No reaction
-
Dim to value
A parameter for adjusting the value appears.
-
State like before bus power failure
Scene function
The scene function can be activated or deactivated here; it is
only available in the "Dimmer" operating mode. If this function is
activated, the parameter page "Dimmer x: Scene function" ap-
pears for further configuration of scenes 1-16. The further func-
tionality is explained in section G.
Automatic mode
Automatic mode is only available in the "Dimmer" function. If this
mode is selected, the following objects become visible:
Group Object Dimmer A
Type KNX
Size
Direction
GO 179 Dimmer A: Automatic Mode -
Activate
1.001
1 Bit
From/To
KNX
GO 180 Dimmer A: Autom. dimming abs.
- Set value
5.001
1 Byte
From KNX
Group Object Dimmer B
Type KNX
Size
Direction
GO 239 Dimmer B: Automatic Mode -
Activate
1.001
1 Bit
From/To
KNX
GO 240 Dimmer B: Autom. dimming abs.
- Set value
5.001
1 Byte
From KNX
Group Object Dimmer C
Type KNX
Size
Direction
GO 299 Dimmer C: Automatic Mode -
Activate
1.001
1 Bit
From/To
KNX
GO 300 Dimmer C: Autom. dimming abs.
- Set value
5.001
1 Byte
From KNX
Group Object Dimmer D
Type KNX
Size
Direction
GO 359 Dimmer D: Automatic Mode -
Activate
1.001
1 Bit
From/To
KNX
GO 360 Dimmer D: Autom. dimming abs.
- Set value
5.001
1 Byte
From KNX
When using automatic mode, the dimmer can be controlled via
object 180, 240, 300 or 360, e.g. for light control or daylight-de-
pendent basic lighting.
In automatic mode, the dimmer can be manually overridden by
dimming on/off, dimming rel., dimming value, scene, slumber
function or sequencer. During manual override, values of object
180, 240, 300 or 360 are ignored, each manual override restarts
the fallback time.
After the fallback time set in the parameter has elapsed, the val-
ues received on object 180, 240, 300 or 360 are processed
again.
Via object 179, 239, 299 or 359, the automatic can be switched
on or off at any time, it also serves as a state object for auto-
matic mode.
Slumber function
The slumber function is only available in the "Dimmer" operating
mode. The slumber function offers 2 different fade times each for
switching on and off via object. If this function is activated, a new
parameter page appears, which is explained in section H.
Lock function
The lock function can be activated or deactivated here.
This function is available in both "Dimmer" and "Staircase func-
tion" operating modes. If this function is activated, a new param-
eter page appears for further configuration, which is explained in
Section I in more detail.
D.
Dimmer A: Dimmer
Dimmer B: Dimmer
Dimmer C: Dimmer
Dimmer D: Dimmer
Object Dimming on/off
For switching the dimmers, the following objects are available, if
they have been activated via parameters:
Group Object Dimmer A
Type KNX
Size
Direction
GO 171 Dimmer A: Dimming on/off -
Switch
1.001
1 Bit
From KNX
Group Object Dimmer B
Type KNX
Size
Direction
GO 231 Dimmer B: Dimming on/off -
Switch
1.001
1 Bit
From KNX
Group Object Dimmer C
Type KNX
Size
Direction
GO 291 Dimmer C: Dimming on/off -
Switch
1.001
1 Bit
From KNX
Group Object Dimmer D
Type KNX
Size
Direction
GO 351 Dimmer D: Dimming on/off -
Switch
1.001
1 Bit
From KNX
Behavior on ON telegram (when dimmer is off)
If the dimmer is switched off, this parameter can be used to con-
figure the behavior when switching on via object 171, 231, 291
or 351.
It is available:
-
No reaction
-
Dim to fix value