2019 WEINZIERL ENGINEERING GmbH
Page 39/41
The time is continuously updated by the de-
vice through its internal timers, but compo-
nent tolerances always result in a deviation
from the actual time. Therefore, the current
time should be sent to the device by a pre-
cise timer at least twice a day in order to
keep the deviation as small as possible.
-
Start after last trigger
Here you can specify the time interval to wait after the
previous activation before executing the step. This
start condition is not available for step 1.
Start time
Here either the time day or the waiting time can be specified for
the execution of the current step, if a timed start condition is
used.
Start by ON/OFF telegram
When using this start condition, a separate object is available for
each step:
Group Object Dimmer A
Type KNX
Size
Direction
GO 195-226 Dimmer A: Sequence Step
x on/off - Switch
1.001
1 Bit
From KNX
Group Object Dimmer B
Type KNX
Size
Direction
GO 255-286 Dimmer B: Sequence Step
x on/off - Switch
1.001
1 Bit
From KNX
Group Object Dimmer C
Type KNX
Size
Direction
GO 315-346 Dimmer C: Sequence Step
x on/off - Switch
1.001
1 Bit
From KNX
Group Object Dimmer D
Type KNX
Size
Direction
GO 375-406 Dimmer D: Sequence Step
x on/off - Switch
1.001
1 Bit
From KNX
An ON telegram to one of these objects activates the respective
step, the sequence is then continued according to its configura-
tion from this step onwards.
An OFF telegram also activates this step, but resets the se-
quence at the same time.
Start by scene number
When using this start condition, the following object becomes
visible:
Group Object Dimmer A
Type KNX
Size
Direction
GO 191 Dimmer A: Sequence scene -
Activate step
18.001
1 Byte
From KNX
Group Object Dimmer B
Type KNX
Size
Direction
GO 251 Dimmer B: Sequence scene -
Activate step
18.001
1 Byte
From KNX
Group Object Dimmer C
Type KNX
Size
Direction
GO 311 Dimmer C: Sequence scene -
Activate step
18.001
1 Byte
From KNX
Group Object Dimmer D
Type KNX
Size
Direction
GO 371 Dimmer D: Sequence scene -
Activate step
18.001
1 Byte
From KNX
A telegram with the set scene on this object activates the respec-
tive step, the sequence is then continued according to its config-
uration from this step onwards.
All steps with this start condition are controlled by this object.
Action
When the step is activated, the configured function is executed,
the following functions are available for selection:
-
None
No function is executed, for example this can be used
to implement a switch-on delay for a sequence.
-
Start loop
The sequence continues from a previous step. Param-
eters for the initial step of the loop and the number of
loops become visible.
-
Send scene number
When using this function, the following object becomes
visible:
Group Object Dimmer A
Type KNX
Size
Direction
GO 192 Dimmer A: Se-
quence scene - Send
scene
18.001
1 Byte
To KNX
Group Object Dimmer B
Type KNX
Size
Direction
GO 252 Dimmer B: Se-
quence scene - Send
scene
18.001
1 Byte
To KNX
Group Object Dimmer C
Type KNX
Size
Direction
GO 312 Dimmer C: Se-
quence scene - Send
scene
18.001
1 Byte
To KNX
Group Object Dimmer D
Type KNX
Size
Direction
GO 372 Dimmer D: Se-
quence scene - Send
scene
18.001
1 Byte
To KNX
A parameter for the scene number to be sent becomes
visible. When the step is activated, this scene number
is sent via the object.
All steps send the scene number via this object, if this
function is used for the respective step.
-
Brightness
Parameters for brightness and fade time become visi-
ble. When this step is activated, the dimmer dims from
the current brightness value to the specified brightness
with the parameterized fade time. This time is related
to a complete dimming process of 0-100%.
K.
Logic / Timer
Function 1 - 16
These channels contain additional functions such as timing and
logic. All these 16 additional functions are identical.
The following options are selectable:
-
Disabled
-
Timer
-
Logic
Function type (Disabled)
If the function type is set to "Disabled", no timer or logic specific
parameters and group objects are available.
Function type (Timer)
The timer-specific parameters and group objects are available.
Function type (Logic)
The logic-specific parameters and group objects are available.