These additional logic and timer functions can be
linked to one another by means of the associated
group objects. This also allows to create complex
structures. For this purpose, the output of a function is
set to the same group address as the input of the next
function.
L.
Function 1 - 16 (Timer)
Function name (10 Characters)
The function name can be chosen freely.
The name is visible in the group object entry in the ETS soft-
ware. This makes it easier to work with the associated group ob-
jects, because the given name is displayed there as a label.
Timer type (Switch-on delay)
A timer that switches ON after duration defined in
‘Delay time [s]’ parameter.
The output value can be inverted by parameter
‘Output’ (Not inverted / inverted).
Input
-------1------------------0----------
Output
-------|-T-1--------------0----------
Group Object
Type KNX
Size
Direction
Timer - Switch-on delayed - Input
1.002
1 Bit
From KNX
Timer - Switch-on delayed - Output
1.002
1 Bit
To KNX
Timer type (Switch-off delay)
A timer that switches OFF after duration defined in
‘Delay time [s]’ parameter.
The output value can be inverted by parameter
‘Output’. (Not inverted / inverted)
Input
-------1------------------0----------
Output
-------1------------------|-T-0------
Group Object
Type KNX
Size
Direction
Timer - Switch-off delayed - Input
1.002
1 Bit
From KNX
Timer - Switch-off delayed - Output
1.002
1 Bit
To KNX
Timer type (Switch-on and -off delay)
A timer that switches ON and OFF after duration defined in ‘De-
lay time [s]’ parameter.
The output value can be inverted by parameter
‘Output’. (Not inverted / inverted)
Input
-------1------------------0----------
Output
-------|-T-1--------------|-T-0------
Group Object
Type KNX Size
Direction
Timer - Switch-on/off delayed - Input
1.002
1 Bit
From KNX
Timer - Switch-on/off delayed - Output
1.002
1 Bit
To KNX
Timer type (Impulse (Staircase))
Timer with impulse that
– after being switched
ON
–
automati-
cally switches OFF
after a defined duration defined in
‘Delay time [s]’ parameter.
The output value can be inverted by parameter
‘Output’. (Not inverted / inverted)
Input
-------1------------------0----------
Output
-------1-T-0-------------------------
Each timer can be stopped by sending the opposite
value to its input group object.
For example:
An already started switch on timer can be stopped by
sending OFF (0) to its input group object.
M. Function 1 - 16 (Logic)
Function name (10 Characters)
The function name can be chosen freely.
The name is visible in the group object entry in the ETS soft-
ware. This makes it easier to work with the associated group ob-
jects, because the given name is displayed there as a label.
Group Object
Type KNX
Size
Direction
Logic
– Gate input A - Input
1.002
1 Bit
From KNX
Logic
– Gate input B - Input
1.002
1 Bit
From KNX
Logic
– Gate output – Output
1.002
1 Bit
To KNX
Gate type (AND gate)
The output is triggered on (1), if both inputs are switched on (1).
Gate type (OR gate)
The output is triggered on (1), if one or both inputs are switched
on (1).
Gate type (XOR gate)
The output is triggered on (1), if the two inputs are not equal.
Gate type (NAND gate)
The output is triggered on (1), if one or both inputs are switched
off (0).
Gate type (NOR gate)
The output is triggered on (1), if both inputs are switched off (0).
Gate type (XNOR gate)
The output is triggered on (1), if both inputs are equal.
Gate type (INVERTER)
Group Object
Type KNX Size
Direction
Timer - Switch-impulse (staircase) - In-
put
1.002
1 Bit
From KNX
Timer - Switch-impulse (staircase) - Out-
put
1.002
1 Bit
To KNX