2019 WEINZIERL ENGINEERING GmbH
Page 13/41
-
1 h
-
2 h
-
Without time limit
Color while orientation light
This color is dimmed to at the end of the delay time when orien-
tation light is used.
Fade time for orientation light
This fade time is active when the staircase function dims to ori-
entation light. The period refers to a complete dimming process
of 0-100%.
Reaction on OFF telegram
Here it can be set how the staircase function behaves in the
event of an OFF telegram. The following options are available:
-
Ignore
No reaction of the channel on OFF telegram
-
Switch off
Switch to switch-off value from the parameters
-
Switch to switch-off delay
The delay time is started with OFF telegram.
-
Switch to orientation light
The orientation light phase is started with OFF tele-
gram.
-
Switch to orientation light/switch off
With 1. OFF telegram the orientation light phase is
started, with 2. OFF telegram it is dimmed to switch-off
value.
Color on switching off the staircase function (day)
This color is dimmed to in day mode if the staircase function is
switched off after the delay time or via OFF telegram on object
11.
Color on switching off the staircase function (night)
This color is dimmed to in night mode if the staircase function is
switched off after the delay time or via OFF telegram on object
11.
Fade time for switching off
This fade time is active when the staircase function dims to the
switch-off value. The period refers to a complete dimming pro-
cess of 0-100%.
G. RGB A: Dimming curve
This parameter page is used for fine adjustment of the dimmer to
different light sources.
All parameters on this page only affect the PWM value
of the output, not the dimming or output status value.
Dimming curve
Here it can be specified which PWM values are output by the
dimming outputs when the dimming channel has reached a cer-
tain color. The curve affects all outputs of the channel. The fol-
lowing options are available:
-
Linear
-
Logarithmic
-
User defined
-
Gamma
Gamma correction according to the formula:
Gamma is adjustable via parameter from 1.00 to 5.00
-
DALI
Function based on DALI with the formula:
Outputs at x%
For the "Linear", "Logarithmic" and "User defined" dimming
curves, these values determine the PWM values of a dimming
output at the specified dimming value. Values between the spec-
ified points are calculated and output linearly. As an example, a
dimming output with dimming curve "Logarithmic" behaves ac-
cording to the following graph:
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
0%
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
Gamma = 2
Gamma = 3,5
Gamma = 5
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
0%