2019 WEINZIERL ENGINEERING GmbH
Page 34/41
This dimming time is active when the brightness is increased by
values received via object 174, 234, 294 or 354. The time period
refers to a complete dimming process of 0-100%.
Fade time while dimming darker with object
This dimming time is active when the brightness is decreased by
values received via object 174, 234, 294 or 354. The time period
refers to a complete dimming process of 0-100%.
E.
Dimmer A: Staircase function
Dimmer B: Staircase function
Dimmer C: Staircase function
Dimmer D: Staircase function
This parameter page can be used to implement a staircase func-
tion with optional orientation light. The staircase function can be
overridden by the lock function. It has the following objects:
Group Object Dimmer A
Type KNX
Size
Direction
GO 171 Dimmer A: Staircase function -
Trigger
1.010
1 Bit
From KNX
GO 175 Dimmer A: Day/Night - Switch
1.001
1 Bit
From KNX
Group Object Dimmer B
Type KNX
Size
Direction
GO 231 Dimmer B: Staircase function -
Trigger
1.010
1 Bit
From KNX
GO 235 Dimmer B: Day/Night - Switch
1.001
1 Bit
From KNX
Group Object Dimmer C
Type KNX
Size
Direction
GO 291 Dimmer C: Staircase function -
Trigger
1.010
1 Bit
From KNX
GO 295 Dimmer C: Day/Night - Switch
1.001
1 Bit
From KNX
Group Object Dimmer D
Type KNX
Size
Direction
GO 351 Dimmer D: Staircase function -
Trigger
1.010
1 Bit
From KNX
GO 355 Dimmer D: Day/Night - Switch
1.001
1 Bit
From KNX
Day mode is triggered with an ON telegram on object 175, 235,
295 or 355, night mode with an OFF telegram. After a restart, the
device is in day mode.
Dimming value on switching on the staircase function (day)
This value is used in day mode when the staircase function is
switched on via ON telegram to object 171, 231, 291 or 351.
Dimming value on switching on the staircase function
(night)
This value is used in night operation when the staircase function
is switched on via ON telegram to object 171, 231, 291 or 351.
Fade time for switching on
This dimming time is active when the staircase function is
switched on via ON telegram to object 171, 231, 291 or 351. The
period refers to a complete dimming process of 0-100%.
Delay time for staircase function
After the delay time has elapsed, the dimmer is dimmed to the
switch-off or orientation light value depending on the parameter
setting.
Reaction on ON telegram
This parameter determines the behavior after switching on the
staircase function via ON telegram on object 171, 231, 291 or
351: When "Switch on" is set, the channel remains switched on
after ON telegram until the follow-up time is started via OFF tele-
gram. In the setting "Switch to delay time", the channel enters
the delay time immediately after the ON telegram.
Delay time retriggerable
If it is set that the delay time is started with ON telegram, this pa-
rameter determines whether only the 1. ON telegram on object
171, 231, 291 or 351 starts the delay time, or also any further.
If it is set that the delay time is started with OFF telegram, this
parameter determines whether only the 1. OFF telegram on ob-
ject 171, 231, 291 or 351 starts the delay time, or also any other
if the staircase function is already in the delay time.
Orientation light after delay time
This parameter can be used to set whether the dimmer dims to
switch-off value or to orientation light at the end of the delay
time, as well as the duration of the orientation light.
It is available:
-
Disabled
-
1 s
-
2 s
-
5 s
-
10 s
-
30 s
-
1 min
-
2 min
-
5 min
-
10 min
-
20 min
-
30 min
-
1 h
-
2 h
-
Without time limit
Dimming value while orientation light
This value is dimmed to at the end of the delay time when orien-
tation light is used.
Fade time for orientation light
This fade time is active when the staircase function dims to ori-
entation light. The period refers to a complete dimming process
of 0-100%.
Reaction on OFF telegram
Here it can be set how the staircase function behaves in the
event of an OFF telegram. The following options are available:
-
Ignore
No reaction of the channel on OFF telegram
-
Switch off
Switch to switch-off value from the parameters