background image

©

2019 WEINZIERL ENGINEERING GmbH 

Seite 1/41

 

 

Operation and installation manual

 

KNX IO 534 (4D)

 

(Art. # 5314)

 

Dimming actuator with 4 PWM dimming outputs 
Application with RGB / RGBW / Tunable White support 
 

 
 

 

KNX IO 534 (4D) 

 
Application area 

The KNX IO 534 (4D) is a compact RGB / RGBW / Tunable 
White dimming actuator with 4 PWM outputs. 

The dimming actuator can be used e.g. for LED panels or stripes 
with RGB / RGBW / Tunable White configuration or as 4 inde-
pendent PWM dimmer channels. Every configuration allows con-
trolling the channel by switching, rel. dimming and dimming 
value. 

Several comfort functions are integrated as well, including 
scenes, slumber fading, staircase light and sequencer. 

Two push buttons and three LEDs allow a local operation and a 
visualization of the device state. 

In addition to the output channels the device includes 16 inde-
pendent functions for logic or timer control. 

 

1.  Installation and connection 

The KNX IO 534 is designed for installation on a DIN rail (35 
mm) with a width of 1 units (18 mm). An installation-friendly de-
sign with pluggable screw terminals helps to reduce the cost of 
commissioning. It features the following controls and displays:

 

        

 

 

This device is powered by the KNX bus. An external power sup-
ply is not necessary. 

 
 The device is not working without bus power.

 

 

A. 

KNX Programming mode

 

The KNX programming mode is activated/deactivated either by 
pressing the flushed KNX programming button 

❸ 

or by simulta-

neously pressing the buttons 

❼ 

and 

. Accessing the pro-

gramming mode via the device front buttons can be enabled / 
disabled via the ETS® by changing the value of 

Prog. mode on 

device front.

 

When the programming mode is active, the programming LED 

❷ 

and LED Ch/M 

 light red. 

 

B. 

Manual operation and status display 

The LED Ch/M 

 

lights up or flashes if the device is success-

fully powered by the KNX bus. 

The channel for manual operation can be selected by pressing 
button A 

 or B 

❽ 

short. The selected channel is indicated by 

a continuous light or cyclic flashing of LED Ch/M 

 in green, 

where the number of flash cycles indicates the number (A=1, 
B=2, C=3, D=4) of the channel. On continuous light all channels 
are controlled simultaneously in manual operation. 

Pressing button A 

 or B 

❽ 

for a long time switches to manual 

operation for the selected channel of the dimming actuator. This 
is indicated by continuous light or cyclic flashing of the LED 
Ch/M 

 in orange. The flashing frequency corresponds again 

to the channel selection. 

In manual operation, the respective channel can be switched on 
by pressing button On 

❼ 

and switched off by pressing button 

Off

 ❽

 short. In addition, it can be dimmed brighter with long but-

ton press on 

❼ 

and darker with long button press on 

The manual operation mode can be exit by pressing the buttons 
(Esc) 

 

and

 

 simultaneously. 

LED A 

 indicates the status of the dimming actuator. It lights 

up when the channel is switched on and is off when the channel 
is switched off. 

EN 

 KNX bus connector 

 

Programming LED 

 

Button f. programming mode 

 LED All (multicolor)  

 LED Ch/M (multicolor)  

 LED Ch (multicolor)  

 Button Up/On 

 Button Dn/Off 

 Pluggable screw terminals 

 
 

 

Summary of Contents for KNX IO 534 (4D)

Page 1: ...ly pressing the buttons and Accessing the pro gramming mode via the device front buttons can be enabled disabled via the ETS by changing the value of Prog mode on device front When the programming mode is active the programming LED and LED Ch M light red B Manual operation and status display The LED Ch M lights up or flashes if the device is success fully powered by the KNX bus The channel for man...

Page 2: ...green Device is working in standard operation mode After activation of manual operation all channels can be operated LED flashes 1x green The device is currently loaded by the ETS or after activation of manual operation channel A can be op erated LED flashes 2x green After activation of manual operation channel B can be operated LED flashes 3x green After activation of manual operation channel C c...

Page 3: ...ed is reduced Alternatively the devices can also be mounted at a small distance approx TE 9 mm Suitable spacers for the top hat rail are available on the market for this purpose Safety shutdown The dimming actuator has an electronic fuse for overcurrent and overtemperature In both error cases the output is switched off and can be switched on again via a command if the error is no longer present In...

Page 4: ...This parameter affects all dimmer outputs Device configuration Here the general configuration of the device can be set the fol lowing are available for selection 1 x RGB The device is operated as an RGB dimmer 3 output channels are occupied 1 further output channel can be used as a general dimmer or remain deactivated 1 x RGBW The device is operated as an RGBW dimmer for which all 4 output channel...

Page 5: ...vated the state objects trans mit with a time interval of at least 1 second if the color attribute assigned to the object has changed by at least 1 or if a dim ming process has been completed Behavior on bus power failure The behavior of the output in the event of bus power failure can be configured here The following options are selectable No reaction Switch to color A parameter for adjusting the...

Page 6: ...irection GO 12 RGB A Red on off Switch 1 001 1 Bit From KNX GO 15 RGB A Green on off Switch 1 001 1 Bit From KNX GO 18 RGB A Blue on off Switch 1 001 1 Bit From KNX Behavior on ON telegram This parameter can be used to configure the behavior when switching on via the respective object It is available No reaction Dim to fix value Value on ON telegram With suitable parameterization this value is act...

Page 7: ...the brightness is decreased via rel ative dimming with object 13 16 or 19 The period refers to a complete dimming process of 0 100 Object value color Red abs Object value color Green abs Object value color Blue abs The following objects are used to control the 3 colors via the dim ming value if they have been activated via parameters Group Object Type KNX Size Direction GO 14 RGB A Red dimming abs...

Page 8: ...m KNX Day mode is triggered with an ON telegram on the object night mode with an OFF telegram After a restart the device is in day mode Telegrams on object 30 affect all activated day night switches of the RGB channel In addition it can be determined when the colors become active after receiving a telegram on this object it is available Disabled Switch on day night telegram Immediately after recep...

Page 9: ...de time on OFF telegram This fade time is active when an OFF telegram is received The period is related to a complete dimming process of 0 100 Day night switching When using this function the following object is visible for switching between day night mode Group Object Type KNX Size Direction GO 30 RGB A Day Night Switch 1 001 1 Bit From KNX Day mode is triggered with an ON telegram on the object ...

Page 10: ...minimum satura tion can be reached via object 26 If a value below the minimum value is received the dimmer is controlled with the minimum value Minimal value for changing saturation with object This parameter can be used to configure which maximum satura tion can be reached via object 26 If a value below the maximum value is received the dimmer is controlled with the maximum value Fade time while ...

Page 11: ...ived via object 27 Switch on next on off telegram The currently active value is not used until the next switch on off telegram via object 27 There is a separate switch on and switch off brightness for night mode in the parameters in day mode the always visible bright ness values are used Brightness on ON telegram night If the dimmer is in night mode this value is activated by ON tele gram via obje...

Page 12: ... KNX Day mode is triggered with an ON telegram on the object night mode with an OFF telegram After a restart the device is in day mode Color on switching on the staircase function day This color is used in day mode when the staircase house func tion is switched on by telegram to object 11 Color on switching on the staircase function night This color is used in night mode when the staircase house f...

Page 13: ... mode if the staircase function is switched off after the delay time or via OFF telegram on object 11 Fade time for switching off This fade time is active when the staircase function dims to the switch off value The period refers to a complete dimming pro cess of 0 100 G RGB A Dimming curve This parameter page is used for fine adjustment of the dimmer to different light sources All parameters on t...

Page 14: ...er between 1 and 64 can be assigned to the scene No scene numbers may be assigned twice I RGB A Slumber function If the slumber function is active the following object is visible Group Object Type KNX Size Direction GO 43 RGB A Slumber function Trig ger 1 001 1 Bit From KNX Target color while switching on the slumber function This color is reached by the channel after completion of the dim ming pr...

Page 15: ...hanged by the priority object Behavior at end This parameter defines which state the output should set if the lock deactivates The following options are selectable No reaction Switch to color A parameter for adjusting the color appears State before lock This restores the original state before the lock was ac tivated Telegrams received during the lock are ig nored State without lock Here the state ...

Page 16: ...itching off any further acti vation of a step after switching off is disabled until the sequencer is switched on again by object 54 Step 1 32 When a step is activated its parameters for configuration ap pear In the text box at the top right with the content Step x you can enter your own name for the step This designation serves for better orientation of the user and has no influence on the func ti...

Page 17: ...nes the functionality of the actuator the fol lowing options are selectable Dimmer In this operating mode scene function automatic op eration slumber function and disable function are available In the Dimmer function objects for switch ing on off relative dimming and absolute value can be configured Staircase function The parameter page TW A Staircase function or TW B Staircase function is display...

Page 18: ... A Autom dimming abs Set color temperature via scaling 5 001 1 Byte From KNX GO 34 TW A Autom dimming abs Set color temperature 7 600 2 Byte From KNX Group Object TW B Type KNX Size Direction GO 110 TW B Automatic mode Acti vate 1 001 1 Bit From To KNX GO 111 TW B Autom dimming abs Set brightness value 5 001 1 Byte From KNX GO 112 TW B Autom dimming abs Set color temperature together with brightne...

Page 19: ...r lower than the parameterized brightness for OFF tele gram the device is already switched off by the 1 OFF telegram Fade time on OFF telegram This fade time is active when an OFF telegram is received The period refers to a complete dimming process of 0 100 Day night switching When using this function the following objects are visible for switching between day night mode Group Object TW A Type KNX...

Page 20: ...Group Object TW B Type KNX Size Direction GO 93 TW B Color temperature via brightness dimming abs Set value 5 001 1 Byte From KNX Minimal value for changing brightness by object This parameter can be used to configure which minimum bright ness can be reached via object 13 or 93 If a value below the minimum value is received the dimmer is controlled with the minimum value If a value 0 is set here t...

Page 21: ...er is in night mode this value is activated by ON tele gram via object 11or 91 and suitable parameterization Color temperature on OFF telegram night If the dimmer is in night mode this value is activated by OFF tel egram via object 11 or 91 and suitable parameterization Fade time for day night switching This fade time is only active if switching on day night telegram is used If switching on next o...

Page 22: ...when receiving 100 via objects 17 and 97 If a value between 0 100 is received the color temperature is calculated and output linearly on basis of the set limit values Fade time while changing color temperature with object This fade time is active when the color temperature is changed by receiving a value via object 17 and 97 The period refers to a complete dimming process of 0 100 Adjust brightnes...

Page 23: ...lues become active after receiving a telegram on these objects it is available Disabled Switch on day night telegram Immediately after reception of day night switching it is dimmed to the active value according to the last switch on switch off received via object 18 or 98 Switch on next on off telegram The currently active value is not used until the next switch on off telegram via object 18 or 98...

Page 24: ...n This parameter page can be used to implement a staircase func tion with optional orientation light The staircase function can be overridden by the lock function It has the following objects Group Object TW A Type KNX Size Direction GO 11 TW A Staircase function Trig ger 1 010 1 Bit From KNX GO 21 TW A Day Night Switch 1 001 1 Bit From KNX Group Object TW B Type KNX Size Direction GO 91 TW A Stai...

Page 25: ... it can be set how the staircase function behaves in the event of an OFF telegram The following options are available Ignore No reaction of the channel on OFF telegram Switch off Switch to switch off value from the parameters Switch to switch off delay The delay time is started with OFF telegram Switch to orientation light The orientation light phase is started with OFF tele gram Switch to orienta...

Page 26: ...tput with dimming curve Logarithmic behaves ac cording to the following graph The output values are fixed for the Linear and Logarithmic dimming curves and can be freely configured for the User de fined curves If a dimming value of 0 is reached the channel always switches off Adjustment of cold white LED Adjustment of warm white LED The PWM value of the color temperature calculated by the dim ming...

Page 27: ...while switching on the slumber function This color temperature is reached by the channel after comple tion of the dimming process after receiving an ON telegram via object 35 or 115 Target brightness while switching on the slumber function This brightness is reached by the channel after completion of the dimming process after receiving an ON telegram via object 35 or 115 Target color temperature w...

Page 28: ...ter configures which state the output should set if the lock activates The following options are selectable No reaction Switch to state Parameters for adjusting color temperature and bright ness appear This output state can still be changed by the priority object Behavior at end This parameter defines which state the output should set if the lock deactivates The following options are selectable No...

Page 29: ... If the sequencer is in a dimming process it is com pleted Step x The function of the step is executed independent of the other set start conditions of the step Stop immediately If the sequencer is in a dimming process it is stopped Apart from the set behavior when switching off any further acti vation of a step after switching off is disabled until the sequencer is switched on again by object 54 ...

Page 30: ... process of 0 100 Device configuration Common dimmer C Dimmer A General Dimmer B General Dimmer C General Dimmer D General Name 30 Characters An arbitrary name can be assigned for the channel However this should be clear and meaningful this makes it easier to work with the associated group objects because the given name is displayed there as a label If no name is assigned the group ob jects are na...

Page 31: ...ate 1 001 1 Bit From To KNX GO 360 Dimmer D Autom dimming abs Set value 5 001 1 Byte From KNX When using automatic mode the dimmer can be controlled via object 180 240 300 or 360 e g for light control or daylight de pendent basic lighting In automatic mode the dimmer can be manually overridden by dimming on off dimming rel dimming value scene slumber function or sequencer During manual override va...

Page 32: ... triggered with an ON telegram on object 175 235 295 or 355 night mode with an OFF telegram After a restart the device is in day mode In addition it can be determined when the values become active after receiving a telegram on these objects it is available Disabled Switch on day night telegram Immediately after reception of day night switching it is dimmed to the active value according to the last...

Page 33: ...the maximum value Fade time while dimming brighter with object This fade time is active when the brightness is increased by rela tive dimming with object 173 233 293 or 353 The period refers to a complete dimming process of 0 100 Fade time while dimming darker with object This fade time is active when the brightness is decreased by rel ative dimming with object 173 233 293 or 353 The period re fer...

Page 34: ... or 351 Fade time for switching on This dimming time is active when the staircase function is switched on via ON telegram to object 171 231 291 or 351 The period refers to a complete dimming process of 0 100 Delay time for staircase function After the delay time has elapsed the dimmer is dimmed to the switch off or orientation light value depending on the parameter setting Reaction on ON telegram ...

Page 35: ...PWM value of the output not the dimming or output status value Dimming curve Here it can be specified which PWM values are output by the dimming outputs when the dimming channel has reached a cer tain dimming value The following options are available Linear Logarithmic User defined Gamma Gamma correction according to the formula Gamma is adjustable via parameter from 1 00 to 5 00 DALI Function bas...

Page 36: ...Group Object Dimmer A Type KNX Size Direction GO 181 Dimmer A Slumber function Trigger 1 001 1 Bit From KNX Group Object Dimmer B Type KNX Size Direction GO 241 Dimmer B Slumber function Trigger 1 001 1 Bit From KNX Group Object Dimmer C Type KNX Size Direction GO 301 Dimmer C Slumber function Trigger 1 001 1 Bit From KNX Group Object Dimmer D Type KNX Size Direction GO 361 Dimmer D Slumber functi...

Page 37: ...possible to set an initial state without affecting other functions Example of the priority objects In the case of events in public buildings or in restaurants the normal operation can be set into an inoperative state by the lock group object Thus it is possible to lock during the lecture or con cert switches that are accessible to unauthorized persons in or der to prevent unmeant switching Neverth...

Page 38: ...n This step is executed when resuming after manual operation the function of the set step is always executed regardless of its oth erwise set starting conditions Polarity of object Sequence on off This parameter can be used to set the telegram value with which the sequence can be switched on and off via object 194 254 314 or 374 If the sequence is switched off any further activation of a step is d...

Page 39: ...Dimmer D Sequence scene Activate step 18 001 1 Byte From KNX A telegram with the set scene on this object activates the respec tive step the sequence is then continued according to its config uration from this step onwards All steps with this start condition are controlled by this object Action When the step is activated the configured function is executed the following functions are available for...

Page 40: ... Type KNX Size Direction Timer Switch on off delayed Input 1 002 1 Bit From KNX Timer Switch on off delayed Output 1 002 1 Bit To KNX Timer type Impulse Staircase Timer with impulse that after being switched ON automati cally switches OFF after a defined duration defined in Delay time s parameter The output value can be inverted by parameter Output Not inverted inverted Input 1 0 Output 1 T 0 Each...

Page 41: ...ing safety rules must be heeded The device must not be opened For planning and construction of electric installa tions the relevant guidelines regulations and standards of the respective country are to be con sidered The power rating is indicated on the side of the product ETS4 5 Database www weinzierl de en products 534 ets4 Datasheet www weinzierl de en products 534 datasheet CE Declaration www ...

Reviews: