Logical Command and Speed Reference
CFW501 | 7-5
7
P0220 – Local/Remote Selection
Adjustable
Range:
0 = Always Local
1 = Always Remote
2 = Local / Remote HMI Key (LOC)
3 = Local / Remote HMI Key (REM)
4 = Digital Input (DIx)
5 = Serial / USB (LOC)
6 = Serial / USB (REM)
7 = SoftPLC
Factory
Setting:
2
Properties:
cfg
Access groups
via HMI:
I/O
Description:
It defines the command origin source which will select between Local situation and Remote situation, where:
LOC: means Local situation default.
REM: means Remote situation default.
DIx: according to function programmed for digital input in P0263 to P0270.
P0221 – Speed Reference Selection – LOCAL Situation
P0222 – Speed Reference Selection – REMOTE Situation
Adjustable
Range:
0 = HMI Keys
1 = AI1
2 = AI2
3 = AI3
4 = AI1 + AI2 > 0 (Sum AIs > 0)
5 = AI1 + AI2 (Sum AIs)
6 = Serial / USB
7 = SoftPLC
8 = Frequency input (FI)
9 = AI1 > 0
10 = AI2 > 0
11 = AI3 > 0
12 = FI > 0
Factory
Setting:
P0221 = 0
P0222 = 1
Properties:
cfg
Access groups
via HMI:
I/O
Description:
These parameters define the origin source for the speed reference in the Local situation and Remote situation.
Some comments on the options of this parameter:
AIx:
it refers to the analog input signal according to
section 12.1 ANALOG INPUTS on page 12-1
HMI:
the reference value set by the keys and contained in parameter P0121.
AIx > 0:
the negative values of the AIx reference are zeroed.
Summary of Contents for CFW501 V1.8X
Page 2: ......
Page 8: ...Summary...
Page 34: ...General Information 2 4 CFW501 2...
Page 38: ...About the CFW501 3 4 CFW501 3...
Page 42: ...HMI and Basic Programming 4 4 CFW501 4...
Page 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Page 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Page 76: ...Available Motor Control Types 8 4 CFW501 8...
Page 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Page 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Page 148: ...Faults and Alarms 14 12 CFW501 14...