Digital and Analog Inputs and Outputs
CFW501 | 12-5
12
P0235 – Input Filter AI1
P0240 – Input Filter AI2
P0245 – Input Filter AI3
Adjustable
Range:
0.00 to 16.00 s
Factory
Setting:
0.15 s
Properties:
Access groups
via HMI:
I/O
Description:
Each analog input of the inverter is defined by the steps of calculation of signal, OFFSET, gain, filter, function and
value AIx, as shown in
Figure 12.2: Block diagram of the analog inputs – Aix on page 12-5
.
Input
AI1
(*)
AI2
(*)
AI3
(*)
Gain
AI1 – P0232
AI2 – P0237
AI3 – P0242
OFFSET
AI1 – P0234
AI2 – P0239
AI3 – P0244
AI1 – P0235
AI2 – P0240
AI3 – P0245
AI1 – P0018
AI2 – P0019
AI3 – P0020
Function
AI1 – P0231
AI2 – P0236
AI3 – P0241
Filter
Value AIx
(internal)
Signal
AI1 – P0233
AI2 – P0238
AI3 – P0243
(*)
Control terminals available in the Plug-in module.
Figure 12.2:
Block diagram of the analog inputs – Aix
P0233 – Input Signal AI1
P0238 – Input Signal AI2
Adjustable
Range:
0 = 0 to 10 V / 20 mA
1 = 4 to 20 mA
2 = 10 V / 20 mA to 0
3 = 20 to 4 mA
Factory
Setting:
0
Properties:
cfg
Access groups
via HMI:
I/O
Summary of Contents for CFW501 V1.8X
Page 2: ......
Page 8: ...Summary...
Page 34: ...General Information 2 4 CFW501 2...
Page 38: ...About the CFW501 3 4 CFW501 3...
Page 42: ...HMI and Basic Programming 4 4 CFW501 4...
Page 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Page 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Page 76: ...Available Motor Control Types 8 4 CFW501 8...
Page 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Page 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Page 148: ...Faults and Alarms 14 12 CFW501 14...