Digital and Analog Inputs and Outputs
CFW501 | 12-23
12
Table 12.9:
Digital output functions
Value
Output Function
Description
0
Not Used
Digital output inactive.
1
N* > Nx
Active when the speed reference (P0001) is greater than Nx (P0288).
2
N > Nx
Active when the motor speed (P0002) is above Nx (P0288) plus a hysteresis value (P0287) and inactive
when the motor speed (P0002) is below Nx (P0288) minus a hysteresis value (P0287).
3
N < Ny
Active when the motor speed (P0002) is above Ny (P0289) plus a hysteresis value (P0287) and inactive
when the motor speed (P0002) is below Ny (P0289) minus a hysteresis value (P0287).
4
N = N*
Active when the motor speed (P0002) is equal to the seep set in P0292.
5
Zero Speed
Motor speed is below the value set in P0291.
6
Is > Ix
Active if the output current Is (P0003) > Ix (P0290).
7
Is < Ix
Active if the output current Is (P0003) < Ix (P0290).
8
Torque > Tx
Active if the motor torque T (P0009) > Tx (P0293).
9
Torque < Tx
Active if the motor torque T (P0009) < Tx (P0293).
10
Remote
Active if the command is the remote condition (REM).
11
Run
Active if the motor is running (active output PWM pulses) RUN status.
12
Ready
Active if the inverter has no fault.
13
No Fault
Active if the inverter has no fault.
14
No F0070
Active if the inverter has no overcurrent fault (F0070).
15
Not Used
Digital output inactive.
16
No F0021/22
Active if the inverter has no overvoltage or undervoltage fault (F0022 or F0021).
17
No F0051
Active if the inverter is without IGBT overtemperature fault (F0051).
18
No F0072
Active if the inverter is without motor overload fault (F0072).
19
4-20 mA OK
Active if AIx is set for 4 to 20 mA (P0233 and/or P0238 and/or P0243 equal to 1 or 3) and AIx < 2 mA.
20
P0695 Value
Status of the bits 0 to 4 of P0695 activate digital outputs DO1 to DO5, respectively.
21
Clockwise
Active if the inverter direction of rotation is Clockwise.
22
Ride-Through
Active if the inverter is executing the Ride-Through function.
23
Pre-Load OK
Active if the pre-load relay of the DC link capacitors was already activated.
24
With Fault
Active if the inverter has a fault.
25
Hours Enab > Hx
Active when Time Enabled (P0043) is above Hx (P0294).
26
SoftPLC
Activates DOx output according to the SoftPLC memory area. Read the SoftPLC User’s Manual.
27
Not Used
Digital output inactive.
28
F > Fx(1)
Active when the output frequency F (P0005) is above Fx (P0281) plus a hysteresis value (P0282) and
inactive when F (P0005) is below Fx (P0281) minus a hysteresis value (P0282).
29
F > Fx(2)
Active when the output frequency F (P0005) is above Fx (P0281) and inactive when F (P0005) is
below Fx (P0281) minus a hysteresis value (P0282).
30
Not Used
Digital output inactive.
31
Not Used
Digital output inactive.
32
No Alarm
Active when the inverter has no alarm.
33
No F/A
Active when the inverter is without alarm and without fault.
34
F/A Dry Pump
Active when dry pump condition was detected (A0766/F0767).
35
F/A Broken Belt
Active when broken belt condition was detected (A0768 / F0769).
36
F/A Filter maintenance
Active when the filter maintenance condition was detected (A0770 / F0771).
37
Sleep Mode
Active when the inverter has the sleep mode active (A0764).
38
Not Used
Digital output inactive.
39
Drive Bypass Contactor
Digital output inactive.
40
Mains Bypass Contactor
Digital output inactive.
41
Fire Mode
Digital output inactive.
42
Self-tuning
Active when the inverter is performing the self-tuning function.
NOTE!
Refer to
chapter 18 HVAC FUNCTIONS on page 18-1
for further information on options 34, 37, 39
and 41.
Summary of Contents for CFW501 V1.8X
Page 2: ......
Page 8: ...Summary...
Page 34: ...General Information 2 4 CFW501 2...
Page 38: ...About the CFW501 3 4 CFW501 3...
Page 42: ...HMI and Basic Programming 4 4 CFW501 4...
Page 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Page 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Page 76: ...Available Motor Control Types 8 4 CFW501 8...
Page 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Page 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Page 148: ...Faults and Alarms 14 12 CFW501 14...