HVAC Functions
CFW501 | 18-23
18
P1066 – External PID Controller Sampling Time
Adjustable
Range:
0.10 to 60.00 s
Factory
Setting:
0.10 s
Properties:
Access groups
via HMI:
HVAC
Description:
This parameter defines the sampling time of the External PID controller.
P1067 – External PID Controller Proportional Gain
Adjustable
Range:
0.000 to 32.767
Factory
Setting:
1.000
Properties:
Access groups
via HMI:
HVAC
Description:
This parameter defines the proportional gain of External PID controller.
P1068 – External PID Controller Integral Gain
Adjustable
Range:
0.000 to 32.767
Factory
Setting:
0.430
Properties:
Access groups
via HMI:
HVAC
Description:
This parameter defines the integral gain of External PID controller.
P1069 – External PID Controller Derivative Gain
Adjustable
Range:
0.000 to 32.767
Factory
Setting:
0.000
Properties:
Access groups
via HMI:
HVAC
Description:
This parameter defines the derivative gain of External PID controller.
Summary of Contents for CFW501 V1.8X
Page 2: ......
Page 8: ...Summary...
Page 34: ...General Information 2 4 CFW501 2...
Page 38: ...About the CFW501 3 4 CFW501 3...
Page 42: ...HMI and Basic Programming 4 4 CFW501 4...
Page 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Page 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Page 76: ...Available Motor Control Types 8 4 CFW501 8...
Page 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Page 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Page 148: ...Faults and Alarms 14 12 CFW501 14...