HVAC Functions
CFW501 | 18-7
18
P1048 – Broken Belt Detection Motor Torque
Adjustable
Range:
0.0 to 350.0 %
Factory
Setting:
20.0 %
Properties:
Access groups
via HMI:
HVAC
Description:
This parameter defines the motor torque value below which will be detected the broken belt condition
P1049 – Broken Belt Detection Time
Adjustable
Range:
0.00 to 650.00 s
Factory
Setting:
20.00 s
Properties:
Access groups
via HMI:
HVAC
Description:
This parameter defines a time interval required on the broken belt condition active to generate the alarm (A0768)
or fault (F0769) by broken belt.
18.5 FILTER MAINTENANCE ALARM
This parameter group allows the user to configure the filter maintenance alarm operation.
The filter maintenance alarm is intended to alert the user of the need to change the filter system. It has the preventive
maintenance function in the filtration system.
P1050 – Filter Maintenance Alarm Configuration
Adjustable
Range:
0 = Disable
1 = Enable Alarm
2 = Enable Fault
Factory
Setting:
0
Properties:
cfg
Access groups
via HMI:
HVAC
Description:
This parameter defines how the filter maintenance alarm functionality will go act in the CFW501 frequency inverter.
Table 18.3:
Description of filter maintenance alarm configuration
P1050
Description
0
It defines will not be done the counting of operation time for change the filter system. Also resets the operation time
for filter maintenance alarm in P1052 parameter.
1
It defines the counting of operation time for filter maintenance alarm will be enabled and only will generate the alarm
message “A0770: Filter maintenance”, i.e., the CFW501 frequency inverter will continue control the motor.
2
It defines the counting of operation time for filter maintenance alarm will be enabled and will generate the alarm
message “A0770: Filter maintenance” during the motor deceleration and the fault “F0771: Filter maintenance” in the
CFW501 frequency inverter after stopping the motor.
Summary of Contents for CFW501 V1.8X
Page 2: ......
Page 8: ...Summary...
Page 34: ...General Information 2 4 CFW501 2...
Page 38: ...About the CFW501 3 4 CFW501 3...
Page 42: ...HMI and Basic Programming 4 4 CFW501 4...
Page 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Page 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Page 76: ...Available Motor Control Types 8 4 CFW501 8...
Page 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Page 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Page 148: ...Faults and Alarms 14 12 CFW501 14...