HVAC Functions
18-2 | CFW501
18
P0407 – Motor Rated Power Factor
Adjustable
Range:
0.50 to 0.99
Factory
Setting:
0.80
Properties:
cfg, V/f, V VW
Access groups
via HMI:
MOTOR, STARTUP
Description:
Setting of the motor rated power factor.
In order to obtain the proper operation of the energy saving function, the motor power factor must be correctly
set, according to the information on the motor nameplate.
Note:
With the motor nameplate data and for applications with constant torque, the motor optimum efficiency is
normally obtained with the energy saving function active. In some cases, the output current may increase,
and then it is necessary to gradually reduce the value of this parameter to the point in which the current value
remains equal to or below the current value obtained with the function disabled.
For information regarding the actuation of P0407 in the V VW control mode, refer to
.
P0588 – Energy Saving Maximum Torque
Adjustable
Range:
0 to 85 %
Factory
Setting:
60 %
Properties:
cfg, V/f
Access groups
via HMI:
HVAC
Description:
This parameter defines the torque value to activate the operation of the energy saving function.
Setting this parameter to 0 % disables the function.
It is recommended to set this parameter to 60%, but it has to be set according the application requirements.
P0589 – Level of Minimum Applied Voltage
Adjustable
Range:
40 to 80 %
Factory
Setting:
40 %
Properties:
cfg, V/f
Access groups
via HMI:
HVAC
Description:
This parameter defines the minimum voltage value that will be applied to the motor when the energy saving
function is active. This minimum value is relative to the voltage imposed by the V/f curve for a certain speed.
Summary of Contents for CFW501 V1.8X
Page 2: ......
Page 8: ...Summary...
Page 34: ...General Information 2 4 CFW501 2...
Page 38: ...About the CFW501 3 4 CFW501 3...
Page 42: ...HMI and Basic Programming 4 4 CFW501 4...
Page 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Page 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Page 76: ...Available Motor Control Types 8 4 CFW501 8...
Page 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Page 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Page 148: ...Faults and Alarms 14 12 CFW501 14...