HVAC Functions
18-28 | CFW501
18
18.8 HVAC FUNCTIONS LOGICAL STATUS
This parameter group allows the user to monitoring the status of HVAC functions.
P1040 – HVAC Functions Logical Status
Adjustable
Range:
0000h to FFFFh
Factory
Setting:
Properties:
ro
Access groups
via HMI:
HVAC
Description:
This parameter allows the user to monitoring the logical status of HVAC functions. Each bit represents a specific
status.
Table 18.11:
Description of the logical status 1 via communication networks (P1040)
Bits
15 to 9
8
7
6
5
4
3
2
1 and 0
Fu
nc
tio
n
Re
se
rv
ed
E
xt
er
na
l P
ID i
n
au
toma
tic
/
ma
nu
al
S
le
ep
mod
e
M
ai
n P
ID i
n
au
toma
tic
/
ma
nu
al
Fi
lte
r ma
in
te
na
nc
e
B
rok
en
b
elt
D
ry
p
ump
Sh
or
t c
ycle
pr
ot
ec
tio
n
Re
se
rv
ed
Bits
Values
Bit 0 Fire Mode
0:
The inverter is not in Fire Mode.
1:
The inverter is operated in Fire Mode.
Bit 1 Bypass Mode
0
: The inverter is not in Bypass Mode.
1
: The inverter is operated in Bypass Mode.
Bit 2 Short Cycle Protection
0:
Short cycle protection is not active.
1:
Short cycle protection is active.
Bit 3 Dry Pump
0
: Dry pump condition was not detected.
1
: Dry pump condition was detected.
Bit 4 Broken Belt
0
: Broken belt condition was not detected.
1
: Broken belt condition was detected.
Bit 5 Filter Maintenance
0
: Filter maintenance alarm was not detected.
1
: Filter maintenance alarm was detected.
Bit 6 Main PID in Automatic / Manual
0:
It indicates the main PID controller is in automatic mode.
1:
It indicates the main PID controller is in manual mode.
Bit 7 Sleep Mode
0
: The inverter is not in Sleep Mode.
1
: The inverter is operated in Sleep Mode.
Bit 8 External PID in Automatic / Manual
0:
It indicates the external PID controller is in automatic mode.
1:
It indicates the external PID controller is in manual mode.
Bits 9 to 15
Reserved.
Summary of Contents for CFW501 V1.8X
Page 2: ......
Page 8: ...Summary...
Page 34: ...General Information 2 4 CFW501 2...
Page 38: ...About the CFW501 3 4 CFW501 3...
Page 42: ...HMI and Basic Programming 4 4 CFW501 4...
Page 58: ...Identification of the Inverter Model and Accessories 6 4 CFW501 6...
Page 72: ...Logical Command and Speed Reference 7 14 CFW501 7...
Page 76: ...Available Motor Control Types 8 4 CFW501 8...
Page 108: ...Functions Common to all the Control Modes 11 14 CFW501 11...
Page 134: ...Digital and Analog Inputs and Outputs 12 26 CFW501 12...
Page 148: ...Faults and Alarms 14 12 CFW501 14...