Centurion Water Heater- Edge [ii]: Install-Operation-Service
SECTION 9: O2 TRIM OPERATION
OMM-0153_A
• 8/25/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 98 of 131
CEN2000 O
2
Trim Values
MENU ITEM
Minimum
Maximum
Default
Settle Time
0
120 Sec
20 Sec
O
2
Trim Gain
0.1
5.0
0.250
Max Tries
0
100
15
O
2
Target
(must be
between O
2
Upper & O
2
Lower)
18%
3%
8%
5.6%
30%
3%
8%
5.6%
40%
3%
8%
5.8%
50%
3%
8%
5.6%
60%
3%
8%
5.6%
70%
3%
8%
5.6%
80%
3%
8%
5.6%
100%
3%
8%
5.6%
O
2
Lower
(must be at
least 1% lower
than O
2
Upper)
18%
2.5%
5.5%
5.1%
30%
2.5%
5.5%
5.1%
40%
2.5%
5.5%
5.4%
50%
2.5%
5.5%
5.1%
60%
5.1%
70%
2.5%
5.5%
5.1%
80%
5.1%
100%
2.5%
5.5%
5.1%
O
2
Upper
(must be at
least 1% higher
than O
2
Lower)
18%
5.5%
8.5%
6.1%
30%
5.5%
8.5%
6.1%
40%
5.5%
8.5%
6.2%
50%
5.5%
8.5%
6.1%
60%
6.1%
70%
5.5%
8.5%
6.1%
80%
6.1%
100%
5.5%
8.5%
6.1%
O
2
Offset
-3.0
3.0
1.0
CEN2000 O
2
Trim Adjustment Range
CALIBRATION POINT
BLOWER VOLTAGE (Volts)
Minimum
Maximum
Default
18%
2.20
2.85
2.50
30%
3.20
3.85
3.50
40%
3.70
4.50
4.10
50%
3.85
4.65
4.25
60%
4.20
5.00
4.60
70%
4.50
5.40
5.00
80%
5.20
6.10
5.70
100%
6.70
7.60
7.20