Centurion Water Heater- Edge [ii]: Install-Operation-Service
SECTION 5: INITIAL START-UP
OMM-0153_A
• 8/25/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 53 of 131
1.
Go to:
Advanced Setup
→
Unit
→
Application Configuration.
Figure 5-14: Application Configuration Screen
2. Set the Operating Mode to
Constant Setpt
.
3. Set the
Setpoint
to the desired value, adjustable from 60°F to 170°F (15.6°C to 76.7°C).
4. Set the
Setpoint
Low Limit
, adjustable from 40°F to 245°F (4.4°C to 118.3°C) and
Setpoint
High Limit
(40°F to 220°F, 4.4°C to 104.4°C) to the desired values.
5. Depending on whether the site contains any storage tanks, set
DHW Tank Config
to
No
Tanks,
One Tank
or
Two Tanks
.
5.6.2 Remote Setpoint Mode
In this mode the unit adjusts the setpoint in response to a remote signal. You must specify how
the unit will communicate with the remote source. To set the unit to
Remote Setpoint
mode:
1. Go to:
Advanced Setup
→
Unit
→
Application Configuration
.
Figure 5-15: Application Configuration Screen
2. Set the
Operating Mode
to
Remote Setpoint
.
3. Set the
Remote Signal
to the source of the remote signal:
•
4-20 Ma
•
1-5 V
•
0-20 mA
•
Network
•
BAS
•
0-5 V
•
PWM Input
4. Set the
Setpoint
Low Limit
and
Setpoint
High Limit
to the desired values.
5. Depending on whether the site contains any storage tanks, set
DHW Tank Config
to
No
Tanks,
One Tank
or
Two Tanks
.
6. If
Remote Signal
is set to
Network
, set
Unit Address
to the unit’s network address.