SECTION 8: WATER HEATER MANAGEMENT
OMM-0153_A
• 8/25/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 93 of 131
Figure 8-17: Actuator PC Board Components
NOTE: DO NOT press Auto-Stroke (Reset) button
. Doing so may alter actuator calibration.
Depress and hold brass clutch button to manually rotate valve.
C A U T I O N !
Power must be removed from the Actuator prior to attempting to manual override. Failure to
observe this precaution may damage the Actuator.
A manual override is provided for use in setup or power failure situations. The override is
operated with a standard hex wrench (included) (see Fig 8-16). To manually open or close the
valve, disconnect the 5-pin connector on the Actuator to ensure 24 VDC power is not supplied.
8.10.1 Sequencing Valve Operating Characteristics
The Sequencing Valve is powered by 24 VDC power supply. The unit has a 5-pin molex valve
harness and the valve has a mating 5-pin plug and play connector. The 5 pins are:
1. +24VDC
2. -24VDC
3. 4-20mA (Control Signal)
4. Common
5. 0-10V (Feedback)
During normal Water Heater Management (WHM), a control signal of less than (<)
– 4mA will
rotate the valve to the fully open (90°) position. Conversely, a control signal of 20 mA will rotate
the valve to the fully closed (0°) position. The Sequencing Valve will send a status of the Valve
(open/close) as a feedback signal (0
–10 VDC) to the Edge Controller.