Centurion Water Heater- Edge [ii]: Install-Operation-Service
SECTION 8: WATER HEATER MANAGEMENT
OMM-0153_A
• 8/25/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 84 of 131
Operating Controls
→
Valve Configuration Parameters
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
Select Output
Aout 2
Read Only
Select the output you want to configure.
Output Signal Type
Current
Read Only
Select the output signal type of the selected output.
Control Mode
On/Off
Read Only
Select the Control Mode for the selected output (Standard Setup)
Valve Feedback
Enabled/Disabled
Disabled
Allows Valve Feedback functionality to be enabled;
Valve Feedback Status
appears.
Valve Feedback Timer
30 Sec.
240 Sec.
60 Sec.
The amount of time for the valve to open before returning an error.
Valve Feedback Status
Open, Close
Read Only
Displays the status of the selected valve.
Figure 8-9: Operating Controls: Valve Configuration Screen
Operating Controls
→
Lead/Lag Control Parameters
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
Lead/Lag Setting
Run Hours, Unit Size,
Select Lead/Lag
Run Hours
Specify how the Lead and Lag units will be selected.
Run Hours
25
225
72
Specify the number of hours after which the Lead unit is rotated.
Lead Unit
0
16
0
Specify the address of the Lead unit.
Lag Unit
0
16
16
Specify the address of the Lag unit.