Centurion Water Heater- Edge [ii]: Install-Operation-Service
SECTION 6: SAFETY DEVICE TESTING
OMM-0153_A
• 8/25/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 63 of 131
6.9 SSOV PROOF OF CLOSURE SWITCH CHECK
The SSOV (shown in Figure 6-7) contains the
Proof of Closure
switch. The
Proof of Closure
switch circuit is checked as follows:
1.
Set the Controller’s
Enable/Disable
switch to
Disable
.
2. Go to
Main Menu
→
Diagnostics
→
Manual Run
and enable
Manual Mode
.
3. Set the valve position
between 25% and 30%
using the
+
(Plus) and
–
(Minus) controls.
4. Loosen the SSOV cover screw and remove cover to access wiring connections.
5. Disconnect wire #1304
from the SSOV to “open” the Proof of Closure switch circuit.
6. The unit should fault and display
SSOV Switch Open
.
7. Replace wire #1304 and press the
CLEAR
button.
8.
Set the Controller’s
Enable/Disable
switch to
Enable
to start the unit.
9. Remove the wire again when the unit reaches the purge cycle and
Purging
is displayed.
10. The unit should shut down and display
SSOV Fault During Purge
.
11. Replace the wire on the SSOV and press the
CLEAR
button. The unit should restart.
6.10 PURGE SWITCH OPEN DURING PURGE
The
Purge
switch (and
Ignition
switch) is located on the Air/Fuel Valve. To check the switch:
1.
Set the Controller’s
Enable/Disable
switch to
Disable
.
2. Go to
Main Menu
→
Diagnostics
→
Manual Run
and enable
Manual Mode
.
3. Set the valve position
between 25% and 30%
using the
+
(Plus) and
–
(Minus) controls.
4. Remove the Air/Fuel Valve cover by rotating the cover counterclockwise to unlock it.
5. Remove one of the two wires (#1609 or #1610) from the Purge switch (Figure 6-11).
6.
Set the Controller’s
Enable/Disable
switch to
Enable
to start the unit.
7. The unit should begin its start sequence, then shut down and display
Prg Switch Open
During Purge
.
Figure 6-10: Air/Fuel Valve Cover Location