Watlow EZ-ZONE
®
RMC Module
•
54
•
Chapter 3 Operations Page
RMC Module • Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
No Dis-
play
Profile Status
Wait for Event Source
Value 4
Read the present state
of event input 1.
[`off]
Off (62)
[``on]
On (63)
- - - -
5352
0x7A
(122)
1
0x25 (37)
- - - -
22037
uint
R
No Dis-
play
Profile Status
Wait for Analog
Source Value 1
Read the present value
of analog source 1.
-1999.000 to 9999.000
- - - -
5414
0x7A
(122)
1
0x44 (68)
- - - -
22068
float
R
No Dis-
play
Profile Status
Wait for Analog
Source Value 2
Read the present value
of analog source 2.
-1999.000 to 9999.000
- - - -
5416
0x7A
(122)
1
0x45 (69)
- - - -
22069
float
R
No Dis-
play
Profile Status
Wait for Analog
Source Value 3
Read the present value
of analog source 3.
-1999.000 to 9999.000
- - - -
5418
0x7A
(122)
1
0x46 (70)
- - - -
22070
float
R
No Dis-
play
Profile Status
Wait for Analog
Source Value 4
Read the present value
of analog source 4.
-1999.000 to 9999.000
- - - -
5420
0x7A
(122)
1
0x47 (71)
- - - -
22071
float
R
[Ent1]
[Ent1]
Profile Status
*Active Event Out-
put 1
View or change the
event output states.
[`off]
Off (62)
[``on]
On (63)
Off
5306
0x7A
(122)
1
0xE (14)
- - - -
22014
uint
RW
[Ent2]
[Ent2]
Profile Status
*Active Event Out-
put 2
View or change the
event output states.
[`off]
Off (62)
[``on]
On (63)
Off
5308
0x7A
(122)
1
0xF (15)
- - - -
22015
uint
RW
[Ent3]
[Ent3]
Profile Status
*Active Event Out-
put 3
View or change the
event output states.
[`off]
Off (62)
[``on]
On (63)
Off
5310
0x7A
(122)
1
0x10 (16)
- - - -
22016
uint
RW
[Ent4]
[Ent4]
Profile Status
*Active Event Out-
put 4
View or change the
event output states.
[`off]
Off (62)
[``on]
On (63)
Off
5312
0x7A
(122)
1
0x11 (17)
- - - -
22017
uint
RW
[Ent5]
[Ent5]
Profile Status
*Active Event Out-
put 5
View or change the
event output states.
[`off]
Off (62)
[``on]
On (63)
Off
5314
0x7A
(122)
1
0x12 (18)
- - - -
22018
uint
RW
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0
and above .
R: Read
W: Write
E: EEPROM
S: User Set