Watlow EZ-ZONE
®
RMC Module
•
51
•
Chapter 3 Operations Page
RMC Module • Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[`o;u4]
[ o.v4]
Special Output Function
(1 to 4)
Output Value 4
View the value of this
function's Output 4.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - -
4990
[offset 80]
0x87
(135)
1 to 4
0x10 (16)
- - - -
35016
float
R
No Dis-
play
Special Output Function
(1 to 4)
Error 4
View reported cause for
output malfunction.
None (61)
Open (65)
Shorted (127)
Measurement error (140)
Bad calibration data (139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
Can't process (1659)
- - - -
4992
[offset 80]
0x87
(135)
1 to 4
0x11 (17)
- - - -
35017
uint
R
[P;Sta]
[oPEr]
Profile Status Menu
* Some parameters in the Profile Status Menu can be changed for the currently running profile,
but should only be changed by knowledgeable personnel and with caution. Changing parameters
via the Profile Status Menu will not change the stored profile but will have an immediate impact
on the profile that is running.
Changes made to profile parameters in the Profiling Pages will be saved and will also have an
immediate impact on the running profile.
[P;Str]
[P.Str]
Profile Status
Profile Start
1 to 25
1
5280
0x7A
(122)
1
1
204
22001
uint
W
[P;ACr]
[PACr]
Profile Status
Action Request
[nonE]
None (61)
[PAUS]
Pause (146)
[rESU]
Resume (147)
[`End]
Terminate (148)
[ProF]
Profile (77)
None
5300
0x7A
(122)
1
0xB (11)
205
22011
uint
W
[`StP]
[ StP]
Profile Status
Active Step
View the currently run-
ning step.
0 to 250
0 (none)
- - - -
5286
0x7A
(122)
1
4
- - - -
22004
uint
R
[SUb;S]
[SUb.S]
Profile Status
Active Subroutine
Step
View the currently run-
ning subroutine.
0 to 150
0 (none)
- - - -
0x7A
(122)
1
0x37 (55)
- - - -
22055
uint
R
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0
and above .
R: Read
W: Write
E: EEPROM
S: User Set