Watlow EZ-ZONE
®
RMC Module
•
142
•
Chapter 6 Factory Page
RMC Module • Factory Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[SLoC]
[SLoC]
Security Setting
Write Security
Set the write security
clearance level. The
user can access the
selected level and all
lower levels.
Applies regardless of
Password Enable set-
ting. Set the Write
Security clearance
level. The user can
have write access to
the selected level and
all lower levels. If the
Write Security level is
higher than the Read
Lock, the Read Lock
level takes priority.
0 to 5
5
- - - -
0x67 (103)
1
0x0B (11)
- - - -
3011
uint
RWE
[loC;l]
[LoC.L]
Security Setting
Locked Access Level
Determines user level
menu visibility when
Password is enabled.
See Features section
under Password Secu-
rity. This setting is in
addition to Read Lock
and Write Security.
Consider using only
Locked Access Level
and Set Read Lock
and Write Security
to 5.
1 to 5
5
- - - -
- - - -
- - - -
- - - -
- - - -
[roll]
[roLL]
Security Setting
Rolling Password
Applies if Password
Enable is ON. When
power is cycled a new
Public Key will be
displayed.
[`off]
Off
[``on]
On
Off
- - - -
- - - -
- - - -
- - - -
- - - -
[pas;u]
[PAS.u]
Security Setting
User Password
Applies if Password
Enable is ON. Used
to acquire access to
menus made avail-
able through the
Locked Access Level
setting. Do not forget
the password as it is
required to change
Locked Access Level,
Read Lock or Write
Security.
10 to 999
63
- - - -
- - - -
- - - -
- - - -
- - - -
Note:
Some values will be rounded off to fit in the four-character display . Full values can be read
with another interface .
If there is only one instance of a menu, no submenus will appear .
R: Read
W: Write
E: EE-
PROM
S: User
Set