![Watlow EZ-ZONE RMC User Manual Download Page 110](http://html1.mh-extra.com/html/watlow/ez-zone-rmc/ez-zone-rmc_user-manual_3748884110.webp)
Watlow EZ-ZONE
®
RMC Module
•
107
•
Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[SFn;A]
[SFn.A]
Special Output (1 to 4)
Source Function A
Set the type of function
that will be used for this
source.
[nonE]
None (61)
[``ai]
Analog Input (142)
[`C;Pr]
Cool Power, Control
Loop (161)
[`h;Pr]
Heat Power, Control
Loop (160)
[PWr]
Power, Control Loop (73)
[`Lnr]
Linearization (238)
[MAt]
Math (240)
[``pu]
Process Value (241)
[sof;1]
Special Function Output
1 (1532)
[`uAr]
Variable (245)
None
4960
[offset 80]
0x87 (135)
1 to 4
1
182
35001
uint
RWES
[`Si;A]
[ Si.A]
Special Output (1 to 4)
Source Instance A
Set the instance of the
function selected above.
1 to 24
1
4964
[offset 80]
0x87 (135)
1 to 4
3
183
35003
uint
RWES
[`S2;A]
[ SZ.A]
Special Output (1 to 4)
Source Zone A
Set the zone of the func-
tion selected above.
0 to 16
0
4968
[offset 80]
0x87 (135)
1 to 4
5
- - - -
35005
uint
RWES
[SFn;b]
[SFn.b]
Special Output (1 to 4)
Source Function B
Set the type of function
that will be used for this
source.
[nonE]
None (61)
[`C;Pr]
Cool Power, Control
Loop (161)
[`h;Pr]
Heat Power, Control
Loop (160)
[PWr]
Power, Control Loop (73)
[`Lnr]
Linearization (238)
[MAt]
Math (240)
[`uAr]
Variable (245)
None
4962
[offset 80]
0x87 (135)
1 to 4
2
184
35002
uint
RWES
[`Si;B]
[ Si.b]
Special Output (1 to 4)
Source Instance B
Set the instance of the
function selected above.
1 to 24
1
4966
[offset 80]
0x87 (135)
1 to 4
4
185
35004
uint
RWES
[`S2;B]
[ SZ.b]
Special Output (1 to 4)
Source Zone B
Set the zone of the func-
tion selected above.
0 to 16
0
4970
[offset 80]
0x87 (135)
1 to 4
6
- - - -
35006
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S:
User Set