Watlow EZ-ZONE
®
RMC Module
•
116
•
Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[SFn;D]
[SFn.D]
Profile
Source Function D
Set the type of function
that will be used for
this source. Source will
be used in profile step
type "Wait for Process or
Event" as "Event 1"
[none]
None (62)
[ALM]
Alarm (6)
[`CPE]
Compare (230)
[`Ctr]
Counter (231)
[`dio]
Digital I/O (1142)
[Ent;A]
Profile Event Out A
(233)
[Ent;b]
Profile Event Out B
(234)
[Ent;C]
Profile Event Out C
(235)
[Ent;d]
Profile Event Out D
(236)
[Ent;E]
Profile Event Out E
(247)
[Ent;F]
Profile Event Out F
(248)
[Ent;g]
Profile Event Out G
(249)
[Ent;h]
Profile Event Out H
(250)
[`FUn]
Function Key (1001)
[`lgC]
Logic (239)
[tMr]
Timer (244)
[`uAr]
Variable (245))
None
5328
0x7A
(122)
1
0x19 (25)
- - - -
22025
uint
RWE
[`si;d]
[ Si.d]
Profile
Source Instance D
Set the instance of the
function selected above.
1 to 24
1
5336
0x7A
(122)
1
0x1D (29)
- - - -
22029
uint
RWE
[`S2;D]
[ SZ.D]
Profile
Source Zone D
Set the zone of the func-
tion selected above.
0 to 16
0
5344
0x7A
(122)
1
0x21 (33)
- - - -
22033
uint
RWE
[SFn;E]
[SFn.E]
Profile
Source Function E
Set the type of function
that will be used for
this source. Source will
be used in profile step
type "Wait for Process or
Event" as "Event 1"
[nonE]
None (61)
[``Ai]
Analog Input (142)
[CUrr]
Current (22)
[`C;Pr]
Cool Power, Control
Loop (161)
[`h;Pr]
Heat Power, Control
Loop (160)
[PWr]
Power, Control Loop (73)
[`Lnr]
Linearization (238)
[MAt]
Math (240)
[``Pu]
Process Value (241)
[`SP;C]
Set Point Closed, Con-
trol Loop (242)
[`SP;o]
Set Point Open, Control
Loop (243)
[`uAr]
Variable (245)
None
5390
0x7A
(122)
1
0x38 (56)
- - - -
22056
uint
RWE
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S:
User Set