![Watlow EZ-ZONE RMC User Manual Download Page 87](http://html1.mh-extra.com/html/watlow/ez-zone-rmc/ez-zone-rmc_user-manual_3748884087.webp)
Watlow EZ-ZONE
®
RMC Module
•
84
•
Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[`C;;Si]
[ C.Si]
Current (1 to 4)
Output Source In-
stance
With Current Output
Source Instance, set the
output on which the cur-
rent will be monitored.
1 to 12
1
1416
[offset 50]
0x73 (115)
1 to 4
0x13 (19)
150
15019
uint
RWES
[`Lnr]
[`Set]
Linearization Menu
[``Fn]
[ Fn]
Linearization (1 to 4)
Function
Set how this function
will linearize Source A.
[`oFF]
Off (62)
[intr]
Interpolated (1482)
[Stpd]
Stepped (1483)
Off
4528
[offset 70]
0x86 (134)
1 to 4
5
- - - -
34005
uint
RWES
[SFn;A]
[SFn.A]
Linearization (1 to 4)
Source Function A
Set the type of function
that will be used for this
source.
[nonE]
None (61)
[``Ai]
Analog Input (142)
[CUrr]
Current (22)
[`C;Pr]
Cool Power, Control
Loop (161)
[`h;Pr]
Heat Power, Control
Loop (160)
[PWr]
Power, Control Loop (73)
[`Lnr]
Linearization (238)
[MAt]
Math (240)
[``Pu]
Process Value (241)
[`SP;C]
Set Point Closed, Con-
trol Loop (242)
[`SP;o]
Set Point Open, Control
Loop (243)
[`uAr]
Variable (245)
None
4520
[offset 70]
0x86 (134)
1 to 4
1
155
34001
uint
RWES
[`Si;A]
[ Si.A]
Linearization (1 to 4)
Source Instance A
Set the instance of the
function selected above.
1 or 24
1
4522
[offset 70]
0x86 (134)
1 to 4
2
- - - -
34002
uint
RWES
[`S2;A]
[ SZ.A]
Linearization (1 to 4)
Source Zone A
Set the zone of the func-
tion selected above.
0 or 16
0
4524
[offset 70]
0x86 (134)
1 to 4
3
- - - -
34003
uint
RWES
[Unit]
[Unit]
Linearization (1 to 4)
Units
Set the units of the out-
put value.
[`Src]
Source (1539)
[nonE]
None (61)
[`A;tP]
Absolute Temperature
(1540)
[`r;tp]
Relative Temperature
(1541)
[PWr]
Power (73)
[`pro]
Process (75)
[``rh]
Relative Humidty (1538)
Source
4576
[offset 70]
0x86 (134)
1 to 4
0x1D (29)
156
34029
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S:
User Set