![Watlow EZ-ZONE RMC User Manual Download Page 53](http://html1.mh-extra.com/html/watlow/ez-zone-rmc/ez-zone-rmc_user-manual_3748884053.webp)
Watlow EZ-ZONE
®
RMC Module
•
50
•
Chapter 3 Operations Page
RMC Module • Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[`Su;b]
[ Su.b]
Special Output Function
(1 to 4)
Source Value B
View the value of
Source B.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - -
4974
[offset 80]
0x87
(135)
1 to 4
8
- - - -
35008
float
R
[`o;u1]
[ o.v1]
Special Output Function
(1 to 4)
Output Value 1
View the value of this
function's Output 1.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - -
4978
[offset 80]
0x87
(135)
1 to 4
0xA (10)
- - - -
35010
float
R
No Dis-
play
Special Output Function
(1 to 4)
Error 1
View reported cause for
output malfunction.
None (61)
Open (65)
Shorted (127)
Measurement error (140)
Bad calibration data (139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
Can't process (1659)
- - - -
4980
[offset 80]
0x87
(135)
1 to 4
0x0B (11)
- - - -
35011
uint
R
[`o;u2]
[ o.v2]
Special Output Function
(1 to 4)
Output Value 2
View the value of this
function's Output 2.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - -
4982
[offset 80]
0x87
(135)
1 to 4
0xC (12)
- - - -
35012
float
R
No Dis-
play
Special Output Function
(1 to 4)
Error 2
View reported cause for
output malfunction.
None (61)
Open (65)
Shorted (127)
Measurement error (140)
Bad calibration data (139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
Can't process (1659)
- - - -
4984
[offset 80]
0x87
(135)
1 to 4
0x0D (13)
- - - -
35013
uint
R
[`o;u3]
[ o.v3]
Special Output Function
(1 to 4)
Output Value 3
View the value of this
function's Output 3.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - -
4986
[offset 80]
0x87
(135)
1 to 4
0xE (14)
- - - -
35014
float
R
No Dis-
play
Special Output Function
(1 to 4)
Error 3
View reported cause for
output malfunction.
None (61)
Open (65)
Shorted (127)
Measurement error (140)
Bad calibration data (139)
Ambient error (9)
RTD error (14)
Fail (32)
Math error (1423)
Not sourced (246)
Stale (1617)
Can't process (1659)
- - - -
4988
[offset 80]
0x87
(135)
1 to 4
0x0F (15)
- - - -
35015
uint
R
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0
and above .
R: Read
W: Write
E: EEPROM
S: User Set