Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[`ACt]
[`SEt]
Action Menu
[``Fn]
[ Fn]
Action (1 to 8)
Function
Set the action that will
be triggered by this
function.
Note:
The Limit Reset func-
tion is not available in
this menu for firmware
revision 6.0 and above.
To reset a tripped limit
see the section entitled
"
".
[nonE]
None (61)
[USr;r]
User Settings Restore
(227)
[L;Mr]
Limit Reset (82)
[ALM]
Alarm (6)
[`SiL]
Silence Alarms (108)
[`AoF]
Control Loops Off and
Alarms to Non-alarm State
(220)
[`F;AL]
Force Alarm to Occur
(218)
[idLE]
Idle Set Point (107)
[tUnE]
Tune (98)
[MAn]
Manual (54)
[`oFF]
Switch Control Loop
Off (90)
[`r;En]
Remote Set Point En-
able (216)
[`t;dA]
TRU-TUNE+
®
Disable
(219)
[P;diS]
Profile Disable (206)
[P;hoL]
Profile Hold/Resume
(207)
[ProF]
Start Profile (196)
[P;StS]
Profile Start/Stop (208)
None
1584
[offset 20]
0x6E
(110)
1 to 8
3
138
10003
uint
RWES
[``Fi]
[ Fi]
Action (1 to 8)
Function Instance
Set the instance of the
function selected above.
0 to 25
0
1586
[offset 20]
0x6E
(110)
1 to 8
4
139
10004
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S:
User Set