Watlow EZ-ZONE
®
RMC Module
•
45
•
Chapter 3 Operations Page
RMC Module • Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[CUrr]]
[oPEr]]
Current Menu
Note: To use the current sensing feature, Time Base (Setup
Page, Output Menu) must be set to 0 .7 seconds or more .
[`C;hi]
[ C.hi]
Current (1 to 4)
High Set Point
Set the current value
that will trigger a high
heater error state.
-1,999.000 to 9,999.000
50.0
1394
[offset 50]
0x73
(115)
1 to 4
8
- - - -
15008
float
RWES
[`C;Lo]
[ C.Lo]
Current (1 to 4)
Low Set Point
Set the current value
that will trigger a low
heater error state.
-1,999.000 to 9,999.000
0.0
1396
[offset 50]
0x73
(115)
1 to 4
9
- - - -
15009
float
RWES
[`CU;r]
[ CU.r]
RMS Current (1 to 4)
Read
View the most recent
current value moni-
tored by the current
transformer.
-1,999.000 to 9,999.000
- - - -
1380
[offset 50]
0x73
(115)
1 to 4
1
- - - -
15001
float
R
[`C;Er]
[ C.Er]
Current (1 to 4)
Error
View the cause of the
most recent load fault.
[nonE]
None (61)
[Shrt]
Shorted (127)
[open]
Open (65)
- - - -
1382
[offset 50]
0x73
(115)
1 to 4
2
- - - -
15002
uint
R
[`h;Er]
[ h.Er]
Current (1 to 4)
Heater Error
View the cause of the
most recent load fault
monitored by the cur-
rent transformer.
[nonE]
None (61)
[high]
High (37)
[Low]
Low (53)
- - - -
1384
[offset 50]
0x73
(115)
1 to 4
3
- - - -
15003
uint
R
No Dis-
play
Current (1 to 4)
Actual Power
Power delivered to out-
put monitored by CT.
0.0 to 100.0%
- - - -
1418
[offset 50]
0x73
(115)
1 to 4
0x14 (20)
- - - -
15020
float
R
No Dis-
play
Current (1 to 4)
Error Status
View the cause of the
most recent load fault
None (61)
Fail (32)
- - - -
1420
[offset 50]
0x73
(115)
1 to 4
21
- - - -
15021
uint
R
[`Lnr]
[oPEr]
Linearization Menu
[`Su;A]
[ Su.A]
Linearization (1 to 4)
Source Value A
View the value of
Source A.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
- - - -
4526
[offset 70]
0x86
(134)
1 to 4
4
- - - -
34004
float
R
[oFSt]
[oFSt]
Linearization (1 to 4)
Offset
Set an offset to be ap-
plied to this function's
output.
-1,999.000 to 9,999.000°F or
units
-1,128.000 to 5,537.000°C
0
4530
[offset 70]
0x86
(134)
1 to 4
6
- - - -
34006
float
RWES
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0
and above .
R: Read
W: Write
E: EEPROM
S: User Set