Watlow EZ-ZONE
®
RMC Module
•
103
•
Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[`S2;A]
[ SZ.A]
Math (1 to 8)
Source Zone A
Set the zone of the func-
tion selected above.
0 to 16
0
2860
[offset 70]
0x7D
(125)
1 to 8
0xB (11)
- - - -
25011
uint
RWES
[SFn;b;]
[SFn.b]
Math (1 to 8)
Source Function B
Set the type of function
that will be used for this
source.
[nonE]
None (61)
[``Ai]
Analog Input (142)
[CUrr]
Current (22)
[`C;Pr]
Cool Power, Control
Loop (161)
[`h;Pr]
Heat Power, Control
Loop (160)
[PWr]
Power, Control Loop (73)
[`Lnr]
Linearization (238)
[MAt]
Math (240)
[``Pu]
Process Value (241)
[`SP;C]
Set Point Closed, Con-
trol Loop (242)
[`SP;o]
Set Point Open, Control
Loop (243)
[`uAr]
Variable (245)
None
2842
[offset 70]
0x7D
(125)
1 to 8
2
- - - -
25002
uint
RWES
[`Si;B]
[ Si.b]
Math (1 to 8)
Source Instance B
Set the instance of the
function selected above.
1 to 24
1
2852
[offset 70]
0x7D
(125)
1 to 8
7
- - - -
25007
uint
RWES
[`S2;B]
[ SZ.b]
Math (1 to 8)
Source Zone B
Set the zone of the func-
tion selected above.
0 to 16
0
2862
[offset 70]
0x7D
(125)
1 to 8
0xC (12)
- - - -
25012
uint
RWES
[SFn;C]
[SFn.C]
Math (1 to 8)
Source Function C
Set the type of function
that will be used for this
source.
[nonE]
None (61)
[``Ai]
Analog Input (142)
[CUrr]
Current (22)
[`C;Pr]
Cool Power, Control
Loop (161)
[`h;Pr]
Heat Power, Control
Loop (160)
[PWr]
Power, Control Loop (73)
[`Lnr]
Linearization (238)
[MAt]
Math (240)
[``Pu]
Process Value (241)
[`SP;C]
Set Point Closed, Con-
trol Loop (242)
[`SP;o]
Set Point Open, Control
Loop (243)
[`uAr]
Variable (245)
None
2844
[offset 70]
0x7D
(125)
1 to 8
3
- - - -
25003
uint
RWES
[`Si;C]
[ Si.C]
Math (1 to 8)
Source Instance C
Set the instance of the
function selected above.
1 to 24
1
2854
[offset 70]
0x7D
(125)
1 to 8
8
- - - -
25008
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S:
User Set